Eaton / Cutler-HammerEGB2015FFG
Quantity
New
Quantity
Eaton / Cutler-HammerEGB2015FFG
Eaton / Cutler-HammerEGB2040FFG
Eaton / Cutler-HammerEGB2050FFG
Eaton / Cutler-HammerEGB2060FFG
| Brand | Eaton / Cutler-Hammer |
|---|---|
| Part Number | EGB2020FFG |
| Series | EGB |
| Amperage | 20A |
| Poles | 2 |
| Mounting Style | Unit Mount |
| Voltage | 240VAC, 480VAC, 250VDC |
| Phase | 1 |
| AIC Rating | 25kA @ 240VAC, 18kA @ 480VAC, 10kA @ 250VDC |
| Frame Type | EG |
|---|---|
| Terminal Type | Lugs |
| For Use With | Eaton Series G Enclosures, Switchboards, Motor Control Centers, OEM Panels |
| Wire Gauge | 14-1/0 AWG |
| Max Wire | 1/0 AWG |
| Min Wire | 14 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment |
|---|---|
| Accessories | Line and Load Lugs |
| Standards | CSA C22.2 No. 5, IEC 60947-2, UL 489 |
| Approval | CE, CSA, IEC, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Current Limiting, Reverse Feed |
In Eaton Series G nomenclature, the "FF" indicates the breaker is equipped with fixed thermal and fixed magnetic trip elements. The "G" signifies that standard line and load lugs are included from the factory.
This EG-frame breaker is designed for unit mounting in Eaton Series G enclosures, switchboards, motor control centers, and custom OEM control panels. It bolts directly to the chassis or backplate.
This is a unit mount, or feed-thru, circuit breaker. It does not plug onto a panelboard bus. Instead, it is bolted directly to a mounting surface and wired via the line and load lugs.
The included line and load lugs accept wire sizes ranging from 14 AWG to 1/0 AWG. Always torque the terminals to the manufacturer specifications printed on the breaker label.
Yes, Eaton Series G EG-frame breakers support field-installable internal accessories. Shunt trips, undervoltage releases, and auxiliary contacts can be installed in the designated accessory cavities under the breaker cover.
No, this specific model features a fixed thermal and fixed magnetic trip unit. If your system requires adjustable long-time or instantaneous pickup settings for selective coordination, you will need a Series G breaker equipped with an electronic trip unit.
Yes, in addition to its standard AC ratings, this thermal-magnetic breaker is rated for up to 250VDC applications. It provides a 10kA interrupting capacity at 250VDC, making it suitable for DC control circuits and battery systems.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.