| Brand | Eaton / Cutler-Hammer |
|---|---|
| Series | EGH |
| Amperage | 60A |
| Poles | 2 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480VAC, 600Y/347VAC, 250VDC |
| Phase | 1 |
| AIC Rating | 100kA @ 240VAC, 65kA @ 480VAC, 35kA @ 600Y/347VAC, 42kA @ 250VDC |
| Frame Type | EG |
|---|---|
| Terminal Type | Lugs |
| For Use With | Eaton Pow-R-Line Panelboards |
| Wire Gauge | 14-1/0 AWG (Cu/Al) |
| Max Wire | 1/0 AWG |
| Min Wire | 14 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Handle Mechanism |
|---|---|
| Accessories | Load Side Lugs, Mounting Hardware |
| Standards | CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489 |
| Approval | CCC, CE, CSA, IEC, KEMA, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Current Limiting, High Interrupting Capacity, Reverse Feed, Blow-Open Action |
This EG-frame breaker is designed to bolt directly into Eaton Pow-R-Line panelboards, including the PRL1a, PRL2a, and PRL3a series.
Eaton designates the Power Defense PDG12M0060TFFJ as the modern equivalent. It is a Frame 1, 60A, 2-pole breaker that matches the 65kAIC at 480VAC performance of the legacy Series G model.
The factory-installed lugs accommodate wire gauges from 14 AWG up to 1/0 AWG. The terminals are rated for both copper and aluminum (Cu/Al) conductors.
Yes, this thermal-magnetic breaker is rated for 250VDC applications, delivering an interrupting capacity of 42kAIC for DC networks.
It utilizes a bolt-on connection, requiring screws to mount the breaker directly to the panelboard bus. This ensures a secure, vibration-resistant connection typical in commercial and industrial environments.
No, this breaker features a fixed thermal and fixed magnetic (LI) trip unit. Both the long-time overload and instantaneous short-circuit thresholds are factory-set and cannot be adjusted in the field.
As part of the globally rated Series G family, this EG-frame breaker meets UL, CSA, IEC, CCC, and CE requirements, ensuring compliance across a wide range of international safety jurisdictions.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.