Eaton / Cutler-HammerFAZ-D10/3-NA
Quantity
New
Quantity
Eaton / Cutler-HammerFAZ-D10/3-NA
Eaton / Cutler-HammerFAZ-D13/3-NA
Eaton / Cutler-HammerFAZ-C15/3-NA
Eaton / Cutler-HammerFAZ-D30/3-NA
| Brand | Eaton / Cutler-Hammer |
|---|---|
| Part Number | FAZ-B1/3-NA |
| Series | FAZ-NA |
| Amperage | 1A |
| Poles | 3 |
| Mounting Style | DIN Rail |
| Voltage | 480Y/277VAC, 96VDC |
| Phase | 3 |
| AIC Rating | 10kA @ 480Y/277VAC, 10kA @ 96VDC |
| Terminal Type | Box Lugs |
|---|---|
| For Use With | DIN Rail Panels, Industrial Control Panels |
| Wire Gauge | 18-6 AWG |
| Max Wire | 6 AWG |
| Min Wire | 18 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Curve | B |
| Trip Adjustability | Fixed |
| Available Options | Auxiliary Switch, Shunt Trip, Undervoltage Release, Busbar System, Padlock Attachment |
|---|---|
| Standards | CSA C22.2 No. 5, IEC 60947-2, RoHS, UL 489 |
| Approval | ABS, CE, CSA, DNV, IEC, Lloyd's, RoHS, UL, VDE |
| Temp Rating | -25C to 75C |
| Construction Features | Current Limiting, HACR Rated, Reverse Feed, Trip-Free Mechanism, Visual Trip Indicator |
This breaker features a B-curve trip characteristic, meaning its magnetic trip point is 3 to 5 times the rated current. It is designed for applications with low inrush currents, such as lighting, control circuits, and pilot devices.
Yes, it is a UL 489 listed miniature circuit breaker, making it suitable for branch circuit protection in industrial control panels and DIN rail applications.
Yes, power can be fed from either the line or load side of this circuit breaker.
The FAZ-NA series has a module width of 17.5 mm per pole, so this 3-pole breaker requires 52.5 mm of DIN rail space.
Yes, it features a color-coded contact position indicator that displays red when the breaker is ON and green when it is OFF.
Yes, it features a current-limiting design that interrupts fault currents quickly, reducing the peak let-through energy that can damage downstream circuits.
No, it features a trip-free design, meaning the breaker will trip during an overcurrent or short circuit event even if the handle is physically held in the ON position.
No, UL 1077 supplementary protectors cannot be used in place of UL 489 breakers where branch circuit protection is required by code. However, this UL 489 breaker can be used in place of a UL 1077 device.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.