| Brand | Eaton / Cutler-Hammer |
|---|---|
| Part Number | FAZ-B6/3-NA |
| Series | FAZ-NA |
| Amperage | 6A |
| Poles | 3 |
| Mounting Style | DIN Rail |
| Voltage | 480Y/277VAC, 96VDC |
| Phase | 3 |
| AIC Rating | 10kA @ 480Y/277VAC, 10kA @ 96VDC |
| Terminal Type | Box Lugs |
|---|---|
| For Use With | DIN Rail Systems, Industrial Control Panels |
| Wire Gauge | 18-6 AWG (1 wire), 18-10 AWG (2 wires) |
| Max Wire | 6 AWG |
| Min Wire | 18 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Curve | B |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Busbar System, Lockout Attachment |
|---|---|
| Standards | CSA C22.2 No. 5, IEC 60947-2, UL 489 |
| Approval | ABS, CCC, CE, CSA, cULus, DNV, IEC, Lloyd's, RoHS, UL, VDE |
| Temp Rating | -40C to 75C |
| Construction Features | Current Limiting, HACR Rated, Reverse Feed, Trip-Free Mechanism, Visual Trip Indicator |
The B trip curve indicates that the magnetic trip point is set to 3 to 5 times the rated current. This makes it ideal for resistive loads or applications with low inrush currents where wiring protection is the primary concern.
The NA suffix stands for North America. It indicates that the breaker is UL 489 listed and CSA certified for branch circuit protection, unlike standard FAZ breakers which are UL 1077 recognized for supplementary protection only.
Yes, all Eaton FAZ miniature circuit breakers, including the FAZ-NA series, are suitable for reverse feed applications.
The required torque depends on the wire size used. For 18 to 12 AWG wire, torque to 21 lb-in (2.4 Nm). For 10 to 8 AWG wire, torque to 25 lb-in (2.8 Nm). For 6 AWG wire, torque to 36 lb-in (4.0 Nm).
Yes, the FAZ-NA series supports field-installable accessories, including auxiliary switches, alarm switches, and shunt trips. These can be mounted on the side of the breaker without requiring special tools.
Yes, this breaker is dual rated for both AC and DC applications. It carries a 10kAIC interrupting rating at 96VDC, making it suitable for specific control panel DC loads.
The breaker features a spring clip design that allows it to be mounted directly onto a standard 35mm DIN rail.
Yes, it utilizes a trip-free design. This means the breaker will still trip internally during an overcurrent or short circuit event even if the operating handle is physically held in the ON position.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.