Part of Eaton's Quicklag QCR series, this 40A, two-pole miniature circuit breaker provides dependable protection for commercial environments. The unit features a space-saving 1/2-inch width per pole, ideal for high-density control panels. Designed for flexible installation, the breaker utilizes a rear-mounting provision with cable-in/cable-out box lug terminals. It integrates seamlessly into DIN rail setups. Rated for 10 kAIC at 120/240VAC, the device is HACR rated and UL 489 certified.
DIN Rail, OEM Control Panels, Telecom Power Systems
Wire Gauge
14-4 AWG
Max Wire
4 AWG
Min Wire
14 AWG
Protection and operation
Trip Technology
Thermal Magnetic
Trip Function Code
LI
Trip Function
Long-Time, Instantaneous
Trip Adjustability
Fixed
Standards and features
Available Options
Padlock Attachment
Accessories
Line and Load Lugs Included
Standards
CSA C22.2 No. 5, UL 489
Approval
CSA, HACR, UL
Temp Rating
40C
Construction Features
HACR Rated
Product FAQs
6 answers
Can the Eaton QCR2040 be installed in a standard residential load center?
No. The QCR2040 is a cable-in/cable-out breaker designed for DIN rail or rear chassis mounting in OEM control panels and telecom systems. It lacks the plug-on or bolt-on mounting clips required for standard load centers.
How are the line and load wires connected to the QCR2040?
This feed-thru breaker uses fixed box lugs for both the line and load connections. The lugs are designed to accept copper or aluminum wire ranging from 14 AWG to 4 AWG.
What is the difference between Eaton QCR and standard QC circuit breakers?
Both are Quicklag cable-in/cable-out breakers, but their mounting methods differ. The QCR series is built specifically for rear DIN rail mounting, whereas the standard QC series is designed for traditional flat panel mounting.
Is the QCR2040 suitable for telecom power systems?
Yes. The QCR2040 is frequently used in telecom applications because it carries a DC interrupting rating of 3kA at 48VDC and 62.5VDC, in addition to its standard 120/240VAC ratings.
What type of protection does the LI trip function provide?
The LI trip code stands for Long-Time and Instantaneous protection. The thermal element provides long-time protection against sustained overloads, while the magnetic element provides instantaneous tripping during short circuits.
Does the QCR2040 include ground fault or arc fault protection?
No. This is a standard thermal-magnetic circuit breaker. It does not contain the specialized circuitry required for Ground Fault Circuit Interrupter (GFCI) or Arc Fault Circuit Interrupter (AFCI) protection.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.