ABB / General ElectricTHQB1115GFEP
Quantity
New
Quantity
ABB / General ElectricTHQB1115GFEP
ABB / General ElectricTHQB1130GFEP
ABB / General ElectricTHQB2120GFEP
ABB / General ElectricTHQL1120GFEP
| Brand | ABB / General Electric |
|---|---|
| Part Number | THQB1120GFEP |
| Series | THQB |
| Amperage | 20A |
| Poles | 1 |
| Mounting Style | Bolt-On |
| Voltage | 120VAC |
| Phase | 1 |
| AIC Rating | 10kA @ 120VAC |
| Frame Type | THQB |
|---|---|
| Terminal Type | Box Lugs |
| For Use With | GE A-Series Panelboards, GE AQ Lighting Panels |
| Wire Gauge | 14-8 AWG (Cu), 12-8 AWG (Al) |
| Max Wire | 8 AWG |
| Min Wire | 14 AWG (Cu), 12 AWG (Al) |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LIG |
| Trip Function | Long-Time, Instantaneous, Ground Fault |
| Trip Adjustability | Fixed |
| Special Classification | GFEP |
|---|---|
| Available Options | Shunt Trip, Auxiliary Switch, Padlock Attachment |
| Accessories | Load Side Lugs Included |
| Standards | CSA C22.2 No. 5, NEMA AB 1, UL 489 |
| Approval | CSA, HACR, SWD, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, SWD Rated, Quick-Make/Quick-Break, Trip-Free Mechanism |
The THQB1120GFEP is a Ground Fault Equipment Protection (GFEP) breaker with a 30mA trip threshold, designed to protect machinery and heat trace equipment from low-level faults without nuisance tripping. Standard GFCI breakers have a highly sensitive 5mA threshold intended for personnel protection.
No. This is a THQB frame breaker, which uses a bolt-on connection designed for commercial GE A-Series panelboards and AQ lighting panels. Standard residential GE load centers require THQL frame plug-in breakers.
The attached pigtail wire must be routed and secured to the neutral bus bar in your panelboard. This connection powers the internal ground fault sensing circuitry, which is required for the equipment protection to function.
No. Electrical codes require Class A GFCI protection (5mA trip level) for personnel in wet areas like bathrooms and kitchens. This 30mA GFEP breaker is strictly for equipment protection.
GFEP breakers are commonly installed to protect outdoor heat trace cables, snow melting equipment, industrial pumps, and dedicated machinery where a standard 5mA GFCI would be prone to nuisance tripping.
Yes. In addition to the 30mA ground fault sensing, the THQB1120GFEP includes standard thermal-magnetic mechanisms for long-time (overload) and instantaneous (short-circuit) trip functions.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.