| Brand | ABB / General Electric |
|---|---|
| Series | THED |
| Amperage | 60A |
| Poles | 2 |
| Mounting Style | Unit Mount |
| Voltage | 240VAC, 480VAC, 600VAC, 250VDC |
| Phase | 1 |
| AIC Rating | 65kA @ 240VAC, 25kA @ 480VAC, 18kA @ 600VAC, 20kA @ 250VDC |
| Terminal Type | Lugs |
|---|---|
| For Use With | GE Enclosures, Switchboards, Motor Control Centers |
| Wire Gauge | 14 AWG - 3 AWG (Cu), 12 AWG - 1 AWG (Al) |
| Max Wire | 3 AWG (Cu), 1 AWG (Al) |
| Min Wire | 14 AWG (Cu), 12 AWG (Al) |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Padlock Attachment, Alarm Switch |
|---|---|
| Accessories | Line & Load Lugs |
| Standards | UL 489, CSA C22.2 No. 5, NEMA AB-1 |
| Approval | CSA, HACR, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, High Interrupting Capacity, Reverse Feed, Non-Interchangeable Trip, Quick-Make/Quick-Break, Trip-Free Mechanism, Common Trip |
The "WL" suffix indicates that the circuit breaker is factory-equipped with copper/aluminum (Cu/Al) line and load lugs. Breakers ordered without this suffix are typically supplied without lugs.
Yes, GE THED series circuit breakers are suitable for reverse feed applications. This allows power to be supplied to either the line or load terminals without affecting the breaker's protective functions.
Yes, this breaker is suitable for DC applications. It is rated for up to 250VDC with a maximum interrupting capacity of 20kAIC, making it appropriate for specific industrial DC control or distribution circuits.
This E-frame breaker is designed for unit mount installations and is compatible with standard GE enclosures, switchboards, and motor control centers.
For standard factory lugs, the required torque depends on the wire size. Typical values are 35 in-lb for 14 to 10 AWG, 100 in-lb for 8 to 3 AWG, and 150 in-lb for 2 AWG to 1 AWG conductors. Always verify the exact torque rating printed on the installed lug or breaker label.
No, this breaker features a fixed thermal and fixed magnetic trip unit. The long-time and instantaneous trip functions are factory-set and cannot be adjusted in the field.
It is part of the GE E150 product line, commonly referred to as an E-frame molded case circuit breaker. This physical footprint is standardized for breakers rated up to 150 amps across the TEB, TED, and THED series.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.