ABB / General Electric SGHA36AT4400C - 400A 3 Pole Molded Case Circuit Breaker

New

$2,141.65 In Stock

Quantity

Similar Items

Description

Built for demanding industrial applications, this 400-amp Spectra RMS molded case circuit breaker offers advanced LSI electronic trip functions for precise coordination. It installs into GE Spectra Series panelboards and switchboards, providing reliable three-phase power distribution. The SG frame unit boasts a 65kAIC interrupting capacity at 240V, true RMS sensing, and current limiting performance. For future upgrades, it crosses over to the ABB Tmax XT5 platform using a specific retrofit kit.

Specifications

Key specifications
Brand ABB / General Electric
Series SGHA
Amperage 400A
Poles 3
Mounting Style Bolt-On
Voltage 120VAC, 240VAC, 277VAC, 480VAC, 600VAC, 120/240VAC
Phase 3
AIC Rating 65kA @ 120VAC, 65kA @ 240VAC, 35kA @ 277VAC, 35kA @ 480VAC, 25kA @ 600VAC, 65kA @ 120/240VAC
Electrical ratings
Amperage Range 200-400A
Fit and installation
Terminal Type Lugs
For Use With GE Spectra Series Panelboards and Switchboards
Wire Gauge (1) 8 AWG-600 kcmil (Cu/Al) or (2) 2/0 AWG-500 kcmil (Cu/Al)
Max Wire 600 kcmil
Min Wire 8 AWG
Protection and operation
Trip Technology Electronic Trip
Trip Function Code LSI
Trip Function Long-Time, Short-Time, Instantaneous
Trip Adjustability Fixed Thermal, Adjustable Magnetic
Standards and features
Available Options Shunt Trip, Auxiliary Switch, Undervoltage Release, Bell Alarm, Lug Kits, Rating Plugs, Padlock Attachment, Motor Operator
Accessories Lugs Not Included
Standards CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489
Approval CSA, IEC, UL
Temp Rating 40C
Construction Features HACR Rated, Current Limiting, Reverse Feed, True RMS Sensing, Interchangeable Trip Unit

Product FAQs

9 answers
Can I install the SGHA36AT4400C in standard GE A-Series lighting panels?

No, this SG-frame breaker is designed exclusively for GE Spectra Series panelboards and switchboards. It will not fit in standard A-Series panels or residential load centers.

What wire configurations are supported by the lugs on the SGHA36AT4400C?

The terminals support dual configurations. You can terminate a single copper or aluminum conductor ranging from 8 AWG to 600 kcmil, or two conductors ranging from 2/0 AWG to 500 kcmil per phase.

How does the LSI electronic trip unit benefit my installation?

The solid-state LSI (Long-Time, Short-Time, Instantaneous) trip unit allows electricians to fine-tune the breaker's response curve. This adjustability ensures precise selective coordination with upstream and downstream devices in complex electrical systems.

Is the SGHA36AT4400C considered an SG600 frame breaker?

Yes. Although it is configured with a 400A rating plug and sensors, it utilizes the physical footprint and internal components of the GE Spectra RMS SG600 frame size.

Why is this GE Spectra breaker listed with ABB branding?

Following ABB's acquisition of GE Industrial Solutions, the legacy GE Spectra RMS product line transitioned under the ABB brand. The physical breaker and its compatibility remain identical to the original GE specifications.

Do I need to purchase a separate rating plug for the SGHA36AT4400C?

No. While GE Spectra RMS frames often require a separate rating plug to set the continuous amperage, this specific catalog number includes the 400A rating plug pre-installed.

What mounting method does this Spectra RMS breaker use?

The SGHA36AT4400C features a bolt-on connection. It must be bolted directly to the busbars of a compatible Spectra Series panelboard or switchboard using the correct mounting hardware kit.

Can I adjust the trip settings on this breaker while it is energized?

For safety and compliance with NFPA 70E, all adjustments to the LSI electronic trip unit should be made while the breaker is de-energized. Always follow proper lockout and tagout procedures before removing the panel cover.

Is there a modern replacement for the SGHA36AT4400C if I am upgrading my panel?

Yes, ABB offers retrofit kits that allow you to upgrade legacy GE Spectra SG frames to the modern ABB Tmax XT5 platform without replacing the entire panelboard enclosure.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.