ABB / General ElectricSKLA36AT1200
Quantity
New
Quantity
ABB / General ElectricSKLA36AT1200
ABB / General ElectricSKLA36AT0800
ABB / General ElectricSKLB36BB1200
ABB / General ElectricSKLB36BC1200
| Brand | ABB / General Electric |
|---|---|
| Series | SKLA |
| Amperage | 1200A |
| Poles | 3 |
| Mounting Style | Bolt-On |
| Voltage | 120VAC, 240VAC, 277VAC, 480VAC, 600VAC, 120/240VAC |
| Phase | 3 |
| AIC Rating | 100kA @ 120VAC, 100kA @ 240VAC, 65kA @ 277VAC, 65kA @ 480VAC, 42kA @ 600VAC, 100kA @ 120/240VAC |
| Terminal Type | Lugs |
|---|---|
| For Use With | Spectra Series Switchboards, Power Panels |
| Wire Gauge | (4) 250-500 kcmil (Cu/Al) |
| Max Wire | 500 kcmil |
| Min Wire | 250 kcmil |
| Trip Technology | Electronic Trip |
|---|---|
| Trip Function Code | LSI |
| Trip Function | Long-Time, Short-Time, Instantaneous |
| Trip Adjustability | Adjustable |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Bell Alarm, Lug Kits |
|---|---|
| Accessories | Rating Plug (SRPK1200A1200), Lugs Not Included |
| Standards | CSA C22.2 No. 5, IEC 60947-2, UL 489 |
| Approval | CE, CSA, HACR, IEC, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Current Limiting, True RMS Sensing, Interchangeable Rating Plug, Reverse Feed, Solid State, 100% Rated |
This SK-frame breaker is designed for installation in GE and ABB Spectra Series switchboards and power panels.
LSI indicates the electronic trip unit includes adjustable settings for Long-Time, Short-Time, and Instantaneous protection. This allows panel builders to precisely coordinate the breaker with other protective devices in the electrical system.
The terminal lugs on this 1200A breaker accept four 250 to 500 kcmil conductors per phase. They are rated for both copper and aluminum wire.
ABB acquired GE Industrial Solutions. The SKLA36AT212XC is the exact same Spectra RMS circuit breaker, but newer production units will feature the ABB brand name instead of the GE logo.
The SKLA36AT212XC features a bolt-on connection type, requiring it to be securely bolted directly to the busbars of the compatible switchboard or power panel.
Yes, the solid state electronic trip unit is fully adjustable. Electricians can modify the LSI parameters to match the specific load requirements and fault current calculations of the facility.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.