ABB / General ElectricTEYL2030B
Quantity
New
Quantity
ABB / General ElectricTEYL2030B
ABB / General ElectricTEYL2020B
ABB / General ElectricTEYL2035B
ABB / General ElectricTEYL2015B
| Brand | ABB / General Electric |
|---|---|
| Part Number | TEYL2025B |
| Series | TEYL |
| Amperage | 25A |
| Poles | 2 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480Y/277VAC, 125VDC, 250VDC, 120/240VAC |
| Phase | 1 |
| AIC Rating | 100kA @ 240VAC, 65kA @ 480Y/277VAC, 42kA @ 125VDC, 20kA @ 250VDC, 100kA @ 120/240VAC |
| Terminal Type | Lugs |
|---|---|
| For Use With | GE A-Series Lighting Panelboards |
| Wire Gauge | 14-10 AWG (Cu), 12-10 AWG (Al) |
| Max Wire | 10 AWG |
| Min Wire | 14 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Bell Alarm |
|---|---|
| Accessories | Load Lugs |
| Standards | CSA C22.2 No. 5, UL 489 |
| Approval | CSA, HACR, HID, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, HID Rated, Quick-Make/Quick-Break, Common Trip, Non-Interchangeable Trip, High Interrupting Capacity |
This bolt-on breaker is designed specifically for use in GE A-Series lighting panelboards.
No, this is a strictly bolt-on circuit breaker designed for bolt-on panelboards. It cannot be used in load centers that require plug-in or snap-in connections.
The terminals accept 14 to 10 AWG copper wire or 12 to 10 AWG aluminum wire.
Yes, it is rated for DC applications. It provides 42kA interrupting capacity at 125VDC and 20kA at 250VDC.
The LI designation indicates long-time and instantaneous trip functions. This provides standard thermal-magnetic protection against overloads and short circuits.
No, this breaker features fixed thermal and fixed magnetic trip elements. The trip points cannot be adjusted in the field.
ABB acquired GE Industrial Solutions. As a result, Q-Line breakers like the TEYL series are currently manufactured under the ABB brand but remain identical in fit and function to the legacy GE versions.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.