ABB / General ElectricTLB134030
Quantity
Re-Certified
Quantity
ABB / General ElectricTLB134030
ABB / General ElectricTLB134100
ABB / General ElectricTLB234150
ABB / General ElectricTLB234175
| Brand | ABB / General Electric |
|---|---|
| Series | TLB |
| Amperage | 40A |
| Poles | 3 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480VAC |
| Phase | 3 |
| AIC Rating | 65kA @ 240VAC, 50kA @ 480VAC |
| Frame Type | TLB1 |
|---|---|
| Terminal Type | Lugs |
| For Use With | GE Panelboards |
| Wire Gauge | 14-1/0 AWG (Cu/Al) |
| Max Wire | 1/0 AWG |
| Min Wire | 14 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release |
|---|---|
| Accessories | Lugs (Load Side) |
| Standards | UL 489, NEMA AB 1 |
| Approval | UL, CSA |
| Temp Rating | 40C |
| Construction Features | Integrally Fused, Current Limiting, Non-Interchangeable Trip |
This bolt-on breaker is engineered for GE commercial and industrial panelboards. Because panelboard compatibility depends on the specific interior, always verify that the TLB1 frame or Tri-Break series is listed on your panel's official labeling before installation.
The load side lugs accept conductor sizes ranging from 14 AWG to 1/0 AWG. They are dual-rated for both copper and aluminum wire.
The breaker provides a 50kAIC rating when installed in 480VAC systems. If applied in a 240VAC system, the interrupting capacity increases to 65kAIC.
Yes. As a member of the GE Tri-Break family, this breaker features an integrally fused design that provides current-limiting capabilities to protect downstream equipment from extreme fault currents.
No. This breaker utilizes a fixed thermal and fixed magnetic trip unit. It provides standard LI (Long-Time and Instantaneous) protection, meaning neither the thermal overload nor the instantaneous short-circuit trip points can be adjusted in the field.
ABB acquired GE Industrial Solutions, meaning legacy GE breaker lines like the Tri-Break series are now managed by ABB. The TLB134040 maintains the exact same form factor, UL listing, and TLB1 frame specifications regardless of which logo is printed on the casing.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.