Engineered for heavy-duty applications, this 500A molded case circuit breaker supplies dependable thermal-magnetic protection. It incorporates an adjustable magnetic trip for tailored coordination. Designed to mount into Eaton, Westinghouse, and Thomas & Betts L-Frame panelboards, it provides a seamless fit for existing infrastructure. This model is replaced by the LD3500 series. Interrupting 42kA at 240VAC, it safely manages high fault currents. The breaker is HACR rated and includes lugs.
Which panelboards are compatible with the LS360500 circuit breaker?
This breaker is designed to mount into Eaton, Westinghouse, and Thomas & Betts L-Frame panelboards. It serves as a direct fit for maintaining or expanding these specific legacy distribution systems.
What wire sizes are compatible with the terminal lugs on the LS360500?
The included lugs accept two conductors per phase, accommodating wire sizes from 250 kcmil to 500 kcmil. This dual-wire capacity is necessary for 500A applications that require parallel conductors.
How does the adjustable magnetic trip function work on this breaker?
The thermal-magnetic trip unit features a fixed thermal element for long-time overload protection and an adjustable magnetic element. This allows electricians to fine-tune the instantaneous short-circuit response to coordinate with downstream devices.
Can I use the LS360500 to replace a Westinghouse L-Frame breaker?
Yes. Because Thomas & Betts, Westinghouse, and Eaton L-Frame breakers share the same physical footprint and bolt-on mounting style, the LS360500 can be installed in the same enclosures and panelboards.
What are the short-circuit interrupting capabilities of the LS360500?
This breaker can safely clear fault currents up to 42kA at 240VAC, 30kA at 480VAC, and 22kA at 600VAC. These ratings ensure the breaker can handle high-level short circuits in commercial and industrial power systems.
What does the LI trip function code indicate on this breaker?
The LI designation means the breaker provides Long-Time (L) and Instantaneous (I) overcurrent protection. The long-time function protects against sustained overloads, while the instantaneous function clears severe short circuits immediately.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.