Built for industrial applications, the Square D LAL36300-8041 is a 300A, 3-pole molded case circuit breaker. It delivers robust thermal-magnetic protection for heavy-duty systems. This unit-mount breaker installs into Square D switchboards and motor control centers. It is replaced by the LGL36300 model, which requires separate control wire taps. The -8041 suffix indicates factory-installed control wire tapped lugs. It features an adjustable magnetic trip and a 30kAIC rating at 480VAC.
What does the -8041 suffix mean on this Square D breaker?
The -8041 suffix indicates that the breaker comes with factory-installed control wire tapped lugs on both the line and load sides. This allows you to easily connect control power circuits directly at the breaker terminals.
Can I use the LAL36300-8041 to replace an LA36300?
No, they have different mounting styles. The LAL36300-8041 is a unit-mount, feed-thru breaker with line and load lugs. The LA36300 is an I-Line breaker designed to plug directly into a Square D I-Line panelboard bus.
How is the LAL36300-8041 mounted in an enclosure?
This is a unit-mount circuit breaker. It bolts directly to the backpan or mounting plate of a Square D industrial enclosure, switchboard, or motor control center, rather than plugging onto a busbar.
Can I run parallel conductors to the LAL36300-8041 terminals?
Yes, the included lugs support parallel runs. You can terminate up to two 1 AWG to 250 kcmil aluminum or copper conductors per phase, or a single 1 AWG to 600 kcmil conductor.
What does the "LI" trip function mean on this breaker?
The LI designation means the thermal-magnetic trip unit provides Long-Time (L) and Instantaneous (I) protection. The long-time function protects against sustained overloads, while the instantaneous function protects against short circuits.
Is the trip unit on the LAL36300-8041 adjustable?
The thermal (long-time) trip function is fixed at 300A, but the magnetic (instantaneous) trip setting is adjustable. This allows you to fine-tune the short-circuit protection to coordinate with other devices in your system.
Can I use aluminum wire with the LAL36300-8041 lugs?
Yes, the factory-installed lugs are dual-rated for both aluminum (Al) and copper (Cu) conductors. Ensure you apply a listed oxide inhibitor when terminating aluminum wire to prevent corrosion and maintain a secure connection.
Is it safe to adjust the magnetic trip setting while the breaker is energized?
No. For safety and to comply with standard electrical practices, you should always de-energize the circuit breaker and follow proper lockout/tagout (LOTO) procedures before adjusting the instantaneous magnetic trip dial.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 7 reviews.