Skip to main content

Square D LAB36350 Molded Case Circuit Breaker

  • 350A
  • 3 Pole
  • I-Line
Square D LAB36350
Molded Case Circuit Breaker
Brand Square D
SKU LAB36350
Select Item Condition
Earn 1895 SuperPoints
  • 350A
  • 3 Pole
  • I-Line

Quantity

Bulk Pricing
Send your parts list for a volume quote.

Square D LAB36350 - 350A 3 Pole Molded Case Circuit Breaker

New

$1,895.94 Check Stock

Quantity

Similar Items

Description

Delivering 350A of thermal-magnetic protection, the Square D LAB36350 is a 3-pole molded case circuit breaker built for commercial and industrial environments. It features a bolt-on connection for secure integration into high-demand electrical systems. This unit is engineered for Square D I-Line panelboards and switchboards. For modern replacements, it crosses over to the LGA36350. Rated for 600VAC, it provides a 42kAIC interrupting capacity at 240V and includes a Visi-Trip indicator.

Specifications

Key specifications
Brand Square D
Part Number LAB36350
Series LAB
Amperage 350A
Poles 3
Mounting Style I-Line
Voltage 240VAC, 480VAC, 600VAC, 250VDC
Phase 3
AIC Rating 42kA @ 240VAC, 30kA @ 480VAC, 22kA @ 600VAC, 10kA @ 250VDC
Fit and installation
Frame Type LAB
Terminal Type Lugs
For Use With Square D I-Line Panelboards and Switchboards
Wire Gauge 1 AWG-600 kcmil (Al/Cu) or (2) 1 AWG-250 kcmil (Al/Cu)
Max Wire 600 kcmil
Min Wire 1 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed Thermal, Adjustable Magnetic
Standards and features
Available Options Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch
Accessories Load Side Lugs Included
Standards CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489
Approval CE, CSA, IEC, UL
Temp Rating 40C
Construction Features HACR Rated, Mercury Free, PVC Free

Product FAQs

4 answers
How does the LAB36350 connect to compatible panelboards?

It mounts directly to the busbar of Square D I-Line panelboards and switchboards using an I-Line style plug-in connection on the line side, eliminating the need for line-side wire terminations. Mechanical lugs are provided on the load side.

What does the LI trip function code indicate on this breaker?

The LI designation means the thermal-magnetic trip unit provides Long-Time (L) protection for overloads and Instantaneous (I) protection for short circuits. The thermal element is fixed, while the magnetic element is adjustable to suit specific application needs.

Is the LAB36350 part of a current or legacy product line?

The LAB36350 is a legacy L-frame molded case circuit breaker from Square D. While it is part of an older series, it remains fully compatible with standard I-Line panelboards and switchboards.

What safety precautions should be taken before installing this I-Line breaker?

Always de-energize the panelboard or switchboard before installing or removing the breaker. Ensure the I-Line jaws are properly aligned with the busbar and that load-side lug connections are torqued to the manufacturer's specifications to prevent arcing or overheating.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.