Schneider ElectricLGA36400CU31X
Quantity
New
Quantity
Schneider ElectricLGA36400CU31X
| Brand | Square D |
|---|---|
| Part Number | LGA36400CU44X |
| Series | LGA |
| Amperage | 400A |
| Poles | 3 |
| Mounting Style | I-Line |
| Voltage | 240VAC, 480VAC, 600VAC |
| Phase | 3 |
| AIC Rating | 65kA @ 240VAC, 35kA @ 480VAC, 18kA @ 600VAC |
| Frame Type | L |
|---|---|
| Terminal Type | Lugs |
| For Use With | Square D I-Line Panelboards, Square D I-Line Switchboards |
| Wire Gauge | (2) 2/0 AWG-500 kcmil (Al/Cu) |
| Max Wire | 500 kcmil |
| Min Wire | 2/0 AWG |
| Trip Technology | Electronic Trip |
|---|---|
| Trip Function Code | LSIG |
| Trip Function | Long-Time, Short-Time, Instantaneous, Ground Fault |
| Trip Adjustability | Adjustable |
| Trip Unit Model | MicroLogic 6.3A |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, Motor Operator, Communication Module |
|---|---|
| Accessories | MicroLogic 6.3A Trip Unit |
| Standards | CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489 |
| Approval | CCC, CE, CSA, IEC, NEMA, NOM, UL, UKCA |
| Temp Rating | -25C to 70C |
| Construction Features | Current Limiting, HACR Rated, 100% Rated, Mercury Free, PVC Free, Integrated Ammeter |
The C indicates that this circuit breaker is 100% rated. This means it can carry its full 400A continuous current rating without the standard 80% derating, provided it is installed in a properly sized and ventilated enclosure.
This breaker features a Micrologic 6.3A electronic trip unit. The U44X suffix designates an ammeter-equipped trip unit with LSIG (Long-Time, Short-Time, Instantaneous, and Ground-Fault) protection functions.
This breaker features an I-Line style plug-in connection and is designed exclusively for use in Square D I-Line panelboards and switchboards.
The factory-installed lugs accept two 2/0 AWG to 500 kcmil aluminum or copper conductors per phase. Ensure proper torque is applied during installation as specified on the breaker faceplate.
If you are installing this LSIG breaker in a 3-phase, 4-wire system, an external neutral current transformer (NCT) is required to accurately monitor ground-fault currents and prevent nuisance tripping.
The Micrologic 6.3A trip unit features local LED indicators that display the specific cause of the trip, such as an overload, short circuit, or ground fault. This simplifies troubleshooting and reduces downtime.
No. I-Line plug-in circuit breakers have a dedicated plug-on jaw for the line side bus connection and cannot be reverse-fed.
Yes. The Micrologic 6.3A trip unit allows you to adjust the pickup and delay settings for the Long-Time, Short-Time, Instantaneous, and Ground-Fault (LSIG) protection functions to coordinate with other devices in your electrical system.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.