Built for industrial environments, the Square D HGA260351 is a 35A, 2-pole MCCB. As part of the PowerPacT H-Frame lineup, it utilizes fixed thermal and adjustable magnetic trip technology for 600VAC circuits. Designed with a Phase AB connection, this breaker mounts into Square D I-Line panelboards. It is an exact replacement for older FA26035AB and FH26035AB models. Delivering a 65kA rating at 240V, this device includes a Visi-Trip indicator and is HACR rated.
HACR Rated, Current Limiting, Visual Trip Indicator, Non-Interchangeable Trip, Reverse Feed, 80% Rated, Phase Connection AB
Product FAQs
7 answers
How does the HGA260351 connect to the panelboard?
It utilizes the Square D I-Line mounting system. The line side features plug-on jaws that connect directly to the panelboard bus stack, while the load side uses mechanical lugs for wire termination. A mounting bracket secures the breaker to the panel interior.
What does the 1 suffix mean in the HGA260351 catalog number?
The 1 suffix specifies the bus phase connection for this 2-pole I-Line breaker. It indicates that the plug-on jaws are configured to connect to the A and B phases of the panelboard bus.
What interrupting rating does the G designate in the HGA260351 part number?
The G indicates the specific interrupting rating tier within the PowerPacT H-Frame family. It provides a maximum capacity of 65kA at 240VAC, 35kA at 480VAC, and 18kA at 600VAC.
What replacement load lugs are compatible with this breaker?
The standard mechanical load lugs for this 35A H-Frame breaker are part number AL150HD. These lugs accept 14 AWG to 3/0 AWG aluminum or copper conductors.
Can the HGA260351 be installed in a standard Square D QO or Homeline load center?
No. This is an I-Line molded case circuit breaker designed exclusively for commercial I-Line panelboards and switchboards. It will not fit in residential QO or Homeline enclosures.
What protection functions are included in the LI trip unit?
The LI designation stands for Long-Time and Instantaneous trip functions. The thermal-magnetic trip unit provides fixed thermal protection for continuous overloads and adjustable magnetic protection for short-circuit faults.
Is the HGA260351 suitable for reverse feeding in an I-Line panel?
Yes, Square D PowerPacT H-Frame thermal-magnetic breakers can be reverse fed. When used as a backfed main in an I-Line panelboard, the breaker must be explicitly labeled as the Main Breaker to comply with service entrance requirements.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.