Part of the PowerPacT H-frame series, this 35A breaker features a factory-installed I-Line bracket with a BC phase connection. It provides reliable thermal-magnetic protection for commercial distribution systems. Designed to mount into Square D I-Line panelboards, it replaces older FA26035BC and FH26035BC models. The unit accepts 14 to 3/0 AWG wire via standard lug terminals. Delivering 65kAIC at 240VAC, this current-limiting device ensures robust fault clearing and includes Visi-Trip.
HACR Rated, Current Limiting, Visual Trip Indicator, Reverse Feed, Non-Interchangeable Trip, 80% Rated, Phase Connection BC
Product FAQs
7 answers
How does the HGA260354 connect to the electrical system?
It utilizes an I-Line style plug-on connection for the line side, which mounts directly to the bus of Square D I-Line panelboards and switchboards. The load side uses standard mechanical lugs.
What does the "4" suffix mean in the HGA260354 catalog number?
The "4" indicates that this 2-pole breaker is factory-configured for a B and C phase connection on the I-Line bus.
What does the "G" in the HGA260354 catalog number designate?
The "G" specifies the interrupting rating tier within the PowerPacT H-Frame series. It provides a higher interrupting capacity than the standard "D" frame, delivering up to 65kA at 240VAC and 35kA at 480VAC.
Can I use an HDA260354 instead of the HGA260354?
The HDA260354 has a lower interrupting capacity (18kA at 480VAC) compared to the HGA260354 (35kA at 480VAC). You can only substitute the HDA if your system's maximum available fault current is below the HDA rating.
What tool and torque specifications are required for the load-side lugs?
The standard AL150HD lugs require a 3/16-inch hex bit. Tighten 14 to 10 AWG aluminum or copper wire to 50 in-lbs, and 8 to 3/0 AWG wire to 120 in-lbs.
Are the trip settings on the HGA260354 adjustable?
No. This breaker is equipped with a fixed thermal-magnetic trip unit. Both the long-time (thermal) and instantaneous (magnetic) trip functions are factory set and cannot be adjusted in the field.
What safety precautions are required when installing this I-Line breaker?
Installation must be performed by a qualified electrician. Always de-energize the panelboard or switchboard completely and verify power is off before seating the breaker onto the I-Line bus to prevent arc flash hazards.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.