Skip to main content
Expedited shipping available at checkout

Square D LX36125G Molded Case Circuit Breaker

  • 125A
  • 3 Pole
  • I-Line
Square D LX36125G
Molded Case Circuit Breaker
Brand Square D
SKU LX36125G
Select Item Condition
Earn 6019 SuperPoints
  • 125A
  • 3 Pole
  • I-Line

Quantity

Bulk Pricing
Send your parts list for a volume quote.
Square D LX36125G - 125A 3 Pole Molded Case Circuit Breaker

Square D LX36125G - 125A 3 Pole Molded Case Circuit Breaker

New

$6,019.01 In Stock

Quantity

Similar Items

Description

Built for demanding industrial applications, this 125A electronic trip MCCB incorporates LSIG functions to safeguard against ground faults and overcurrents. Designed for Square D I-Line panelboards, the breaker features a plug-on jaw connection. When upgrading, it crosses to the PowerPacT LJA36250U44X with an adapter. With a 65kAIC rating at 480V and a Micrologic trip unit, it offers highly configurable protection settings to optimize electrical system coordination.

Specifications

Key specifications
Brand Square D
Part Number LX36125G
Series LX
Amperage 125A
Poles 3
Mounting Style I-Line
Voltage 240VAC, 480Y/277VAC, 480VAC, 600Y/347VAC, 600VAC
Phase 3
AIC Rating 100kA @ 240VAC, 65kA @ 480Y/277VAC, 65kA @ 480VAC, 35kA @ 600Y/347VAC, 35kA @ 600VAC
Fit and installation
Frame Type LX
Terminal Type Lugs
For Use With Square D I-Line Panelboards and Switchboards
Wire Gauge (1) 1 AWG-600 kcmil (Al/Cu) or (2) 1 AWG-250 kcmil (Al/Cu)
Max Wire 600 kcmil
Min Wire 1 AWG
Protection and operation
Trip Technology Electronic Trip
Trip Function Code LSIG
Trip Function Long-Time, Short-Time, Instantaneous, Ground Fault
Trip Adjustability Adjustable
Standards and features
Available Options Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch
Accessories Lugs (Load Side)
Standards CSA C22.2 No. 5, IEC 60947-2, NEMA AB-1, UL 489
Approval CE, CSA, UL
Temp Rating 40C
Construction Features HACR Rated, High Interrupting Capacity, True RMS Sensing, Non-Interchangeable Trip

Product FAQs

7 answers
What panelboards are compatible with the Square D LX36125G?

This breaker is designed exclusively for use in Square D I-Line panelboards and switchboards. It features an I-Line style plug-on jaw connection that mounts directly to the busbar.

What does the G in the LX36125G catalog number indicate?

The G indicates that the breaker's electronic trip unit includes integral equipment ground fault protection. This completes its LSIG (Long-Time, Short-Time, Instantaneous, and Ground Fault) trip functions.

What type of trip unit is installed in the LX36125G?

It features an adjustable Micrologic electronic trip unit. This provides highly configurable LSIG protection settings to optimize electrical system coordination and overcurrent protection.

What wire sizes are accepted by the lugs on the LX36125G?

The load side lugs can accommodate either a single 1 AWG to 600 kcmil aluminum or copper wire, or two 1 AWG to 250 kcmil aluminum or copper wires per phase.

How does the I-Line connection work on this breaker?

The LX36125G uses a plug-on jaw connection on the line side that snaps directly onto the I-Line panelboard busbar. This eliminates the need for line side wire terminations and speeds up the installation process.

What is the modern replacement for the legacy LX36125G?

For modern upgrades, this legacy LX frame crosses to the PowerPacT L-Frame series, such as the LJA36250U44X, using an I-Line adapter. Always verify trip settings and physical dimensions for your specific application before upgrading.

Does the LX36125G provide personnel ground fault protection?

No. The ground fault function in this LSIG trip unit provides equipment ground fault protection, which operates at higher current thresholds to protect machinery and electrical systems. It is not a Class A GFCI designed for personnel protection.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.

Reviews

5.0
Rated 5.0 out of 5 stars
Based on 1 review
Total 5 star reviews: 1 Total 4 star reviews: 0 Total 3 star reviews: 0 Total 2 star reviews: 0 Total 1 star reviews: 0
Rating
Ratings
1 review
  • SD
    Sergio D.
    Flag of United States
    Reviewing
    Square D LXD1U7 Magnetic Coil
    I recommend this product
    Rated 5 out of 5 stars
    12/24/21
    Professional

    Great work got exactly what I ordered