Engineered for demanding commercial environments, this 800A PowerPacT P-frame breaker delivers precise LSI protection via a Micrologic 5.0A trip unit. It features adjustable long-time, short-time, and instantaneous settings with true RMS sensing. This unit-mount configuration installs into Square D enclosures, QED switchboards, and Model 6 motor control centers. A 100% continuous current rating maximizes circuit capacity, while the built-in ammeter enhances system coordination.
What does the "C" in the PGL36080CU43A catalog number indicate?
The "C" signifies that this circuit breaker is 100% rated. This allows the breaker to carry its full 800A continuous current rating without the standard 80% derating, provided it is installed in a properly sized enclosure with 90 degrees C rated wire sized to the 75 degrees C ampacity column.
What type of trip unit is included with the PGL36080CU43A?
This breaker is equipped with a Micrologic 5.0A electronic trip unit, indicated by the "U43A" suffix. It provides adjustable Long-Time, Short-Time, and Instantaneous (LSI) protection, along with an integrated ammeter for current monitoring.
Can I use the PGL36080CU43A in an I-Line panelboard?
No. The "L" in the PGL prefix indicates this is a unit-mount breaker with lugs on both the line and load sides. For an I-Line panelboard, you would need an I-Line version, such as the PGA or PJA series, which features plug-on line terminations.
What enclosures and switchboards are compatible with this breaker?
The PGL36080CU43A is designed for use in Square D P-Frame enclosures, QED switchboards, and Model 6 Motor Control Centers.
What wire sizes are accepted by the lugs on the PGL36080CU43A?
The factory-installed lugs accept three 3/0 AWG to 500 kcmil aluminum or copper conductors per phase.
Is the PGL36080CU43A suitable for reverse feeding?
Yes. All PowerPacT P-frame circuit breakers, including those with Micrologic electronic trip units, can be reverse fed. They are not restricted to forward-fed applications.
Does this breaker include ground fault protection?
No. The Micrologic 5.0A trip unit provides Long-Time, Short-Time, and Instantaneous (LSI) protection only. If ground fault protection is required, you would need a breaker with a Micrologic 6.0A (LSIG) trip unit, such as the U44A suffix.
What is the frame size of the PGL36080CU43A?
This breaker is built on the 1200A PowerPacT P-frame, but it is equipped with an 800A sensor and rating plug to limit the maximum continuous current to 800 amps.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.