Designed to provide both protection and measurement, the Square D PGL36080U41A is an 800A PowerPacT P-Frame molded case circuit breaker. It features a Micrologic 3.0A electronic trip unit, combining adjustable LI protection with an integrated ammeter for current monitoring. This 3-pole breaker utilizes a unit-mount configuration with lugs, making it a perfect fit for Square D QED switchboards and Model 6 MCCs. With a 35kAIC rating at 480V, it leverages true RMS sensing for accurate response.
Square D QED Switchboards, Square D Model 6 Motor Control Centers, Enclosures
Wire Gauge
(3) 3/0 AWG - 500 kcmil (Al/Cu)
Max Wire
500 kcmil
Min Wire
3/0 AWG
Protection and operation
Trip Technology
Electronic Trip
Trip Function Code
LI
Trip Function
Long-Time, Instantaneous
Trip Adjustability
Adjustable
Trip Unit Model
MicroLogic 3.0A
Standards and features
Available Options
Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Motor Operator, Padlock Attachment, Communication Module
Accessories
Micrologic 3.0A Trip Unit (Factory Installed), Lugs
Standards
CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489
Approval
CE, CSA, IEC, NOM, UL
Temp Rating
-25C to 70C
Construction Features
HACR Rated, 80% Rated, True RMS Sensing, Ammeter
Product FAQs
7 answers
Is the PGL36080U41A rated for 80% or 100% continuous current?
This breaker is a standard-rated device, meaning it is rated for 80% continuous current.
Can the trip unit on the PGL36080U41A be swapped in the field?
Yes, the Micrologic 3.0A trip unit is interchangeable in the field, allowing you to upgrade or change protection functions without replacing the entire breaker frame.
How can I manually test the tripping mechanism on this breaker?
The breaker features an integral push-to-trip button on the front cover, allowing you to manually trip the device to verify mechanical operation.
Does the Micrologic 3.0A trip unit use standard thermal sensing?
No, the electronic Micrologic trip unit utilizes true RMS current sensing, which provides highly accurate protection and response compared to traditional thermal-magnetic sensing.
What does the U41A suffix indicate in the PGL36080U41A catalog number?
The U41A designates that the breaker is equipped with a Micrologic 3.0A electronic trip unit, which includes an integrated ammeter and adjustable Long-Time and Instantaneous (LI) protection functions.
Can I install the PGL36080U41A in an I-Line panelboard?
No, this is a unit-mount breaker with lugs on both ends. It lacks the plug-on jaw connections required for I-Line panelboards. It is intended for QED switchboards, Model 6 MCCs, or standalone enclosures.
What does the L in the PGL36080U41A catalog number signify?
The L indicates that this is a unit-mount breaker supplied with factory-installed lugs on both the line and load sides.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.