Siemens Q1520NC 15/20A Tandem Miniature Circuit Breaker

  • 15/20A
  • 1 Pole
  • Plug-On
Siemens Q1520NC
15/20A Tandem Miniature Circuit Breaker
Brand Siemens
SKU Q1520NC
Select Item Condition
Earn 10 SuperPoints
  • 15/20A
  • 1 Pole
  • Plug-On

Quantity

Bulk Pricing
Send your parts list for a volume quote.
Siemens Q1520NC - 15/20A Tandem Miniature Circuit Breaker

Siemens Q1520NC - 15/20A Tandem Miniature Circuit Breaker

Re-Certified

$10.51 No Stock

Quantity

Similar Items

Description

Specifically manufactured for legacy systems, the Siemens Q1520NC is a non-CTL tandem circuit breaker. It offers independent 15A and 20A circuits within a single-pole footprint, operating at 120/240VAC with a 10kAIC rating. This plug-on breaker lacks a rejection clip, allowing it to mount into older pre-1968 ITE, Gould, and Siemens non-CTL panelboards. Ideal for adding capacity to older enclosures, this space-saving unit replaces the MP1520N and features Insta-Wire connections.

Specifications

Key specifications
Brand Siemens
Part Number Q1520NC-R
Series QT
Amperage 15/20A
Poles 1
Mounting Style Plug-On
Voltage 120/240VAC
Phase 1
AIC Rating 10kA @ 120/240VAC
Fit and installation
Frame Type Q
Terminal Type Lugs
For Use With Siemens Load Centers (Non-CTL), Older ITE/Gould Panels (Pre-1968)
Wire Gauge 14-8 AWG (Cu), 12-8 AWG (Al)
Max Wire 8 AWG
Min Wire 14 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed
Standards and features
Special Classification Tandem
Available Options Padlock Attachment, Handle Tie
Standards HACR, SWD, UL 489
Approval CSA, UL
Temp Rating 40C
Construction Features Space Saver, HACR Rated, SWD Rated, Insta-Wire, Non-CTL

Product FAQs

6 answers
What does the "NC" suffix in the Q1520NC part number indicate?

The "NC" stands for Non-CTL (Circuit Total Limiting). This breaker lacks a rejection clip and is designed specifically for replacement use in older panels (pre-1968) that do not have built-in CTL rejection features.

Can I install the Q1520NC in a modern Siemens load center?

Non-CTL breakers are intended for replacement use only in older panels. Modern load centers require CTL breakers, which feature a rejection clip to prevent exceeding the panel's maximum circuit capacity.

Can this breaker be used to replace older ITE or Gould breakers?

Yes, Siemens QT series breakers are UL listed for use in older ITE and Gould load centers that are rated to accept type QT breakers.

Does the Q1520NC provide 240V power?

No. This tandem breaker provides two independent 120V single-pole circuits (one 15A and one 20A) from a single panel bus stab. It cannot supply 240V power for multi-pole appliances.

Is the Q1520NC rated for HVAC and switching duty applications?

Yes, this thermal-magnetic breaker carries both HACR (Heating, Air Conditioning, and Refrigeration) and SWD (Switching Duty) ratings, making it suitable for HVAC equipment and standard lighting control.

Why must I verify my panel's wiring diagram before installing a Non-CTL tandem breaker?

Non-CTL breakers lack a rejection clip and will physically fit into any standard 1-inch slot. Verifying the wiring diagram ensures the panel is rated for tandem breakers and prevents overloading the panel bus beyond its designed circuit capacity.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.