Built for commercial power systems, the ABB XT1SU3015AYD000XXX is a 15A, 3-pole MCCB. It delivers dependable long-time and instantaneous (LI) protection within the SACE Tmax XT line. This unit mount breaker fits ABB ReliaGear neXT panelboards and SB switchboards. It also serves as a substitute for older Tmax T1 series breakers during facility upgrades. With a 65kA interrupt capacity at 240VAC, this XT1 frame breaker is HACR rated, double insulated, and supports reverse feed operation.
ABB ReliaGear neXT Panelboards, ReliaGear SB Switchboards
Wire Gauge
10 AWG - 2/0 AWG (Cu/Al)
Max Wire
2/0 AWG
Min Wire
10 AWG
Protection and operation
Trip Technology
Thermal Magnetic
Trip Function Code
LI
Trip Function
Long-Time, Instantaneous
Trip Adjustability
Fixed Thermal, Fixed Magnetic
Standards and features
Available Options
Shunt Trip, Auxiliary Switch, Undervoltage Release, Motor Operator, Padlock Attachment
Accessories
Line and Load Lugs Included
Standards
CSA C22.2 No. 5, IEC 60947-2, UL 489
Approval
CE, CSA, cULus, IEC, UL
Temp Rating
-25C to 70C
Construction Features
HACR Rated, Reverse Feed, Double Insulated
Product FAQs
10 answers
What panelboards are compatible with the XT1SU3015AYD000XXX?
This breaker integrates into ABB ReliaGear neXT Panelboards and ReliaGear SB Switchboards. It utilizes the SACE Tmax XT design, which replaced legacy GE Spectra RMS breakers in many modern ABB distribution assemblies.
What wire sizes and materials are accepted by the lugs on this breaker?
When terminating conductors on the XT1SU3015AYD000XXX, the standard lugs accept 10 AWG to 2/0 AWG copper or aluminum wire. Always verify the specific torque requirements printed on the breaker faceplate or ABB installation manual before energizing.
Can I adjust the trip settings on the XT1SU3015AYD000XXX?
No. This specific model features a fixed thermal and fixed magnetic trip unit (LI function). If you require adjustable overload or short-circuit settings, you will need to select a breaker with an electronic trip unit, such as an Ekip DIP, available in other Tmax XT frames.
Is this breaker suitable for DC applications?
Yes, the XT1SU3015AYD000XXX is rated for DC systems up to 250VDC with an interrupting capacity of 42kA. When applying molded case circuit breakers in DC circuits, verify the wiring configuration and series pole requirements specified by ABB for your specific voltage.
Can the XT1SU3015AYD000XXX replace legacy GE Spectra RMS circuit breakers?
Yes. Following ABB's acquisition of GE Industrial Solutions, the SACE Tmax XT series replaced the legacy GE Spectra RMS line. You can install this XT1 breaker into existing GE Spectra panelboards and switchboards by using the appropriate ABB Tmax XT retrofit kit.
How does the XT1SU3015AYD000XXX mount into the panel?
This is a unit-mount circuit breaker. It fastens directly to the mounting pan or chassis using screws, rather than plugging onto busbars. Ensure your ReliaGear assembly is configured for unit-mount XT1 frames.
What does the LI trip function code mean on this ABB breaker?
The LI designation indicates that the thermal-magnetic trip unit provides Long-Time (L) protection for overloads and Instantaneous (I) protection for short circuits. This is the standard protection scheme for general power distribution.
Can I install auxiliary contacts or a shunt trip in the XT1SU3015AYD000XXX?
Yes. The ABB Tmax XT1 frame supports a wide range of internal accessories, including auxiliary contacts (AUX) and shunt opening releases (SOR). These accessories are field-installable and mount directly inside the breaker housing.
Is this 15A ABB breaker suitable for HVAC applications?
Yes. Like most ABB Tmax XT molded case circuit breakers, the XT1SU3015AYD000XXX carries a HACR (Heating, Air Conditioning, and Refrigeration) rating, making it suitable for protecting multi-motor HVAC equipment circuits.
Can the XT1SU3015AYD000XXX be reverse fed?
Yes. ABB Tmax XT1 molded case circuit breakers do not have a line or load restriction. Power can be supplied to either the top or bottom terminals, allowing for reverse feed applications up to the maximum voltage rating.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.