Eaton / Cutler-HammerEGB3110FFG
Quantity
New
Quantity
Eaton / Cutler-HammerEGB3110FFG
Eaton / Cutler-HammerEGB3090FFG
Eaton / Cutler-HammerEGB3080FFG
Eaton / Cutler-HammerEGB3070FFG
| Brand | Eaton / Cutler-Hammer |
|---|---|
| Part Number | EGB3125FFG |
| Series | EGB |
| Amperage | 125A |
| Poles | 3 |
| Mounting Style | Unit Mount |
| Voltage | 240VAC, 480VAC, 250VDC |
| Phase | 3 |
| AIC Rating | 25kA @ 240VAC, 18kA @ 480VAC, 10kA @ 250VDC |
| Terminal Type | Lugs |
|---|---|
| For Use With | Eaton Series G Enclosures, Switchboards, MCCs, Pow-R-Line Panelboards |
| Wire Gauge | 14-1/0 AWG |
| Max Wire | 1/0 AWG |
| Min Wire | 14 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, Handle Lock, Multi-Wire Lugs |
|---|---|
| Accessories | Line and Load Lugs Included |
| Standards | CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489 |
| Approval | CE, CSA, IEC, KEMA, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Current Limiting, Reverse Feed |
The EGB3125FFG is officially replaced by the Eaton Power Defense PDG13C0125TFFJ. The Power Defense series serves as the direct upgrade for legacy Series G EG-frame breakers.
This EG-frame breaker is designed for installation in Eaton Series G enclosures, switchboards, motor control centers (MCCs), and Pow-R-Line panelboards.
Yes, the EGB3125FFG accepts common field-fit internal accessories, including shunt trips, auxiliary switches, undervoltage releases, and alarm switches.
Yes, the EGB3125FFG includes line and load side lug terminals that accept 14 to 1/0 AWG wire, eliminating the need to order separate terminal kits for standard connections.
Yes, in addition to its standard AC ratings, this breaker is rated for 250VDC applications with an interrupting capacity of 10kA.
The EGB3125FFG utilizes a patented contact design with high-speed blow-open action. This minimizes let-through current and limits potential damage to downstream equipment during short-circuit faults.
It features a non-interchangeable thermal-magnetic trip unit with fixed thermal and fixed magnetic settings, providing reliable long-time and instantaneous (LI) overcurrent and short-circuit protection.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.