Built for industrial distribution, the Eaton EHD2010 is a two-pole, 10A molded case circuit breaker from the proven Series C lineup. It delivers 14 kAIC of interrupting capacity at 480VAC and features non-interchangeable trip units for consistent performance. The F-Frame breaker mounts into compatible Eaton panelboards, switchboards, and motor control centers. It is fully HACR and HID rated, making it an excellent choice for specialized lighting and HVAC branch circuits.
This F-frame breaker is designed for installation in Eaton Series C panelboards, such as the PRL3a and PRL4, as well as compatible switchboards and motor control centers.
Can the EHD2010 circuit breaker be reverse fed?
Yes, Eaton Series C F-frame breakers are suitable for reverse feed applications, allowing line power to be connected to either the top or bottom terminals.
What is the difference between the EHD2010 and the FD2010?
Both are 10-amp, 2-pole F-frame breakers with the same physical dimensions, but they have different interrupting capacities. The EHD2010 is rated for 14 kAIC at 480VAC, while the FD2010 is rated for 35 kAIC at 480VAC.
Can the EHD2010 be used in direct current (DC) applications?
Yes, in addition to its standard AC ratings, this breaker is certified for use in DC systems up to 250VDC with a 10 kAIC interrupting capacity.
Does the EHD2010 include ground fault or arc fault protection?
No, this is a standard thermal-magnetic breaker equipped with fixed long-time and instantaneous (LI) trip functions. It does not provide GFCI or AFCI protection.
Is this breaker suitable for HVAC equipment?
Yes, all Eaton Series C F-frame circuit breakers are HACR rated, making them suitable for heating, air conditioning, and refrigeration branch circuits.
Can I use the EHD2010 for high-intensity discharge lighting?
Yes, Eaton F-frame breakers rated between 10 and 50 amps are specifically rated for high-intensity discharge (HID) lighting applications.
Are the trip settings on the EHD2010 adjustable?
No, this breaker features fixed thermal and fixed magnetic trip units that are non-interchangeable and cannot be adjusted in the field.
What type of wire can be used with the standard lugs on this breaker?
The standard lugs on the EHD2010 are rated for both copper and aluminum (Cu/Al) conductors, accepting wire sizes from 14 AWG to 10 AWG.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 14 reviews.