Eaton / Cutler-HammerFAZ-D30/3-NA
Quantity
New
Quantity
Eaton / Cutler-HammerFAZ-D30/3-NA
Eaton / Cutler-HammerFAZ-C15/3-NA
Eaton / Cutler-HammerFAZ-D13/3-NA
Eaton / Cutler-HammerFAZ-D10/3-NA
| Brand | Eaton / Cutler-Hammer |
|---|---|
| Part Number | FAZ-D25/3-NA |
| Series | FAZ-NA |
| Amperage | 25A |
| Poles | 3 |
| Mounting Style | DIN Rail |
| Voltage | 480Y/277VAC, 96VDC |
| Phase | 3 |
| AIC Rating | 10kA @ 480Y/277VAC, 10kA @ 96VDC |
| Frame Type | FAZ |
|---|---|
| Terminal Type | Box Lugs |
| For Use With | DIN Rail Panels, Industrial Control Panels |
| Wire Gauge | 18-6 AWG |
| Max Wire | 6 AWG |
| Min Wire | 18 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Curve | D |
| Trip Adjustability | Fixed |
| Available Options | Auxiliary Switch, Busbar System, Padlock Attachment, Shunt Trip, Undervoltage Release |
|---|---|
| Standards | CSA C22.2 No. 5, IEC 60947-2, UL 489 |
| Approval | ABS, CE, CSA, DNV, HACR, IEC, Lloyd's, RoHS, UL, VDE |
| Temp Rating | -25C to 75C |
| Construction Features | Current Limiting, HACR Rated, Reverse Feed, Trip-Free Mechanism |
The D curve indicates a magnetic trip point of 10 to 20 times the rated current. It is designed for highly inductive loads with high inrush currents, such as motors, transformers, and power supplies, preventing nuisance tripping during startup.
Yes, the FAZ-NA series is UL 489 listed for branch circuit protection. This differs from standard FAZ breakers, which are UL 1077 recognized for supplementary protection only.
Yes, Eaton FAZ-NA miniature circuit breakers are suitable for reverse feed applications, allowing power to be connected to either the line or load side terminals.
The FAZ-NA series accepts a variety of field-installable accessories, including auxiliary contacts, shunt trips, undervoltage releases, busbar systems, and padlock hasps.
Yes, Eaton acquired Moeller, and the FAZ-NA series is the direct continuation of the Moeller FAZ UL 489 product line. The FAZ-D25/3-NA can directly replace the equivalent legacy Moeller part.
It mounts directly onto a standard 35mm DIN rail. The breaker features a modular design with a width of 17.5mm per pole, taking up 52.5mm of total DIN rail space for this 3-pole unit.
Yes, FAZ-NA devices feature a current-limiting design. They interrupt fault currents within one half cycle, reducing the peak let-through energy that can damage downstream circuit components.
Yes, it features a trip-free design, meaning the breaker will trip under fault conditions even if the operating handle is physically held in the ON position.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.