| Brand | Eaton / Cutler-Hammer |
|---|---|
| Series | PDG2 |
| Amperage | 225A |
| Poles | 3 |
| Mounting Style | Panel Mount |
| Voltage | 600VAC, 250VDC |
| Phase | 3 |
| AIC Rating | 65kA @ 240VAC, 35kA @ 480VAC, 18kA @ 600VAC, 10kA @ 250VDC |
| Amperage Range | 90-225A |
|---|
| Frame Type | Complete Breaker |
|---|---|
| Terminal Type | Lugs |
| For Use With | Eaton Power Defense Panelboards, Switchboards, Enclosures |
| Wire Gauge | 4 AWG - 4/0 AWG |
| Max Wire | 4/0 AWG |
| Min Wire | 4 AWG |
| Trip Technology | Electronic Trip |
|---|---|
| Trip Function Code | LSI |
| Trip Function | Long-Time, Short-Time, Instantaneous |
| Trip Adjustability | Adjustable |
| Available Options | Auxiliary Switch, Bell Alarm, Shunt Trip, Undervoltage Release, Padlock Attachment, Handle Lock, Rotary Handle, Motor Operator, Terminal Shields |
|---|---|
| Accessories | Line and Load Lugs Included (PDG2X3TA225) |
| Standards | CSA C22.2 No. 5, IEC 60947-2, UL 489, RoHS |
| Approval | CCC, CE, CSA, IEC, RoHS, UL |
| Temp Rating | -20C to 70C |
| Construction Features | Current Limiting, Globally Rated, RoHS Compliant, HACR Rated, Modbus Communication |
This Frame 2 Power Defense breaker is designed for installation in Eaton Power Defense panelboards, switchboards, and enclosed circuit breaker assemblies.
Yes, the PDG23G0225E2MJ features a PXR 20 electronic trip unit equipped with Modbus RTU and relays, allowing it to communicate with facility management and power monitoring systems.
The standard line and load lugs on this model accept wire gauges ranging from 4 AWG up to 4/0 AWG.
The PXR 20 electronic trip unit allows for adjustable Long-Time, Short-Time, and Instantaneous settings. Adjustments can be made directly on the breaker interface or via a USB connection using Eaton Power Xpert Protection Manager software.
Yes, as a Frame 2 Power Defense breaker, it serves as a direct upgrade and replacement for legacy FD-frame models, such as the FD3225, and utilizes standard line and load lugs.
The Power Defense platform is globally rated, meaning it carries approvals for UL 489, CSA, IEC 60947-2, and CCC standards, making it suitable for both domestic and international applications.
The PXR 20 electronic trip unit provides precise LSI protection and predictive diagnostics, allowing facility managers to monitor breaker health, diagnose power quality issues, and prevent outages before they occur.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.