Eaton / Cutler-Hammer PDG23M0150TFFL - 150A 3 Pole Molded Case Circuit Breaker

Eaton / Cutler-Hammer PDG23M0150TFFL - 150A 3 Pole Molded Case Circuit Breaker

New

$977.67 In Stock

Quantity

Similar Items

Description

Delivering 150A of continuous current, the PDG23M0150TFFL is a 3-pole MCCB from Eaton's Power Defense series. This Frame 2 component provides essential long-time and instantaneous (LI) protection. Built for panel mount applications within Eaton Power Defense panelboards, it can also be used to replace legacy Series C HFD3150 breakers. With a 65 kAIC rating at 480V, this current-limiting breaker features fixed thermal-magnetic trip units. It includes load-side lugs and is RoHS compliant.

Specifications

Key specifications
Brand Eaton / Cutler-Hammer
Series PDG2
Amperage 150A
Poles 3
Mounting Style Panel Mount
Voltage 240VAC, 480VAC, 600VAC, 250VDC
Phase 3
AIC Rating 100kA @ 240VAC, 65kA @ 480VAC, 35kA @ 600VAC, 22kA @ 250VDC
Fit and installation
Frame Type Complete Breaker
Terminal Type Lugs
For Use With Eaton Power Defense Panelboards, Switchboards, Enclosures
Wire Gauge 4 AWG - 4/0 AWG (Al/Cu)
Max Wire 4/0 AWG
Min Wire 4 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed Thermal, Fixed Magnetic
Standards and features
Available Options Auxiliary Switch, Shunt Trip, Undervoltage Release, Alarm Switch, Handle Mechanism
Accessories Load Side Lugs Included
Standards CSA C22.2 No. 5, IEC 60947-2, UL 489, RoHS
Approval CCC, CE, CSA, IEC, RoHS, UL
Temp Rating -20C to 70C
Construction Features Current Limiting, HACR Rated, RoHS Compliant

Product FAQs

8 answers
What types of enclosures and gear is the PDG23M0150TFFL compatible with?

This Power Defense Frame 2 breaker is designed for direct integration into Eaton Power Defense panelboards, switchboards, and standalone enclosures. It is not intended for use in load centers that require plug-on breakers.

Can the PDG23M0150TFFL be used in 3-phase electrical systems?

Yes. As a 3-pole complete molded case circuit breaker, it is designed specifically for 3-phase applications. It supports overcurrent and short-circuit protection across 240V, 480V, and 600V AC networks.

Can I use the PDG23M0150TFFL for DC circuit protection?

Yes, this molded case circuit breaker is rated for continuous DC use up to 250VDC. At this voltage, it provides a 22 kAIC short-circuit interrupting rating.

What wire size and material can I use with the standard lugs?

The terminals on this breaker accept conductors ranging from 4 AWG to 4/0 AWG. The lugs are dual-rated for both aluminum and copper (Al/Cu) wire, allowing flexibility based on your facility's wiring standards.

Are the thermal and magnetic trip elements adjustable in the field?

No, this specific model features fixed thermal and fixed magnetic trip settings. If your application requires field-adjustable long-time or instantaneous pickup curves, you will need a breaker with a Power Xpert electronic trip unit or an adjustable thermal-magnetic unit.

What does the M indicate in the PDG23M0150TFFL part number?

In Eaton's Power Defense nomenclature, the letter M specifies the interrupting rating tier. It confirms the breaker is rated for 65 kAIC at 480VAC and 100 kAIC at 240VAC, which determines its suitability for commercial and industrial systems with high available fault current.

How does the LI trip function protect my electrical system?

The LI (Long-Time and Instantaneous) thermal-magnetic trip unit provides two layers of safety. The thermal element safely trips the breaker during sustained overloads, while the magnetic element reacts immediately to clear high-level short circuits, minimizing equipment damage.

How does this breaker connect to the panelboard bus?

The PDG23M0150TFFL utilizes a bolt-on connection. Rather than plugging onto the bus, it must be physically bolted to the chassis or bus bars of compatible panelboards and switchboards, ensuring a rigid, low-resistance mechanical connection.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.