| Brand | Eaton / Cutler-Hammer |
|---|---|
| Series | PDG3 |
| Amperage | 200A |
| Poles | 3 |
| Mounting Style | Panel Mount |
| Voltage | 240VAC, 480VAC, 600VAC, 250VDC |
| Phase | 3 |
| AIC Rating | 35kA @ 240VAC, 25kA @ 480VAC, 14kA @ 600VAC, 10kA @ 250VDC |
| Amperage Range | 160-200A |
|---|
| Frame Type | Complete Breaker |
|---|---|
| Terminal Type | Lugs |
| For Use With | Eaton Power Defense Frame 3 Panelboards, Enclosures |
| Wire Gauge | (1) 3 AWG - 350 kcmil (Al/Cu) |
| Max Wire | 350 kcmil |
| Min Wire | 3 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Adjustable Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Handle Mechanism, Motor Operator |
|---|---|
| Accessories | Standard Line and Load Terminals (PDG3X3TA350) |
| Standards | CSA C22.2 No. 5, IEC 60947-2, UL 489 |
| Approval | CCC, CE, CSA, IEC, UL, RoHS |
| Temp Rating | -20C to 70C |
| Construction Features | HACR Rated, RoHS Compliant |
Yes, it serves as a functional replacement for legacy Series G JG-frame breakers, such as the JGE3200FAG, and Series C J-frame breakers. Because the Power Defense Frame 3 has different physical dimensions, mounting modifications or retrofit kits may be required when upgrading older panels.
The TFAJ suffix specifies the trip unit and terminal configuration. It indicates a thermal-magnetic trip unit with fixed thermal and adjustable magnetic protection, along with standard line and load side lugs included from the factory.
Yes, the PDG33F0200TFAJ features an adjustable magnetic trip function. This allows electricians to fine-tune the instantaneous short-circuit response for better coordination with downstream protective devices in the electrical system.
This breaker is equipped with the Eaton T297 thermal-magnetic trip unit. It provides reliable long-time and instantaneous (LI) protection for heavy-duty commercial and industrial electrical systems.
The standard line and load lugs on the PDG33F0200TFAJ accept one aluminum or copper wire ranging from 3 AWG to 350 kcmil. Ensure proper torque specifications are followed during installation to prevent thermal issues at the terminals.
This breaker is designed for use in Eaton Power Defense Frame 3 panelboards and compatible industrial enclosures. It is not backward compatible with older Series C or Series G panelboard mounting hardware without the use of specific retrofit kits.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.