Built for demanding commercial and industrial environments, the Eaton PDG33M0250TFAJ is a 3-pole, 250A molded case circuit breaker. As part of the Power Defense series, it delivers dependable long-time and instantaneous (LI) circuit protection. This Frame 3 MCCB mounts into Eaton Power Defense and Pow-R-Line panelboards. It effectively replaces legacy LGH3250FAG and HLD3250 breakers. Delivering 65kAIC at 480VAC, it includes a fixed thermal and adjustable magnetic trip unit with standard lugs.

Specifications

Key specifications
Brand Eaton / Cutler-Hammer
Part Number PDG33M0250TFAJ
Series PDG3
Amperage 250A
Poles 3
Mounting Style Panel Mount
Voltage 240VAC, 480VAC, 600VAC, 250VDC
Phase 3
AIC Rating 100kA @ 240VAC, 65kA @ 480VAC, 35kA @ 600VAC, 22kA @ 250VDC
Fit and installation
Frame Type PDG
Terminal Type Lugs
For Use With Eaton Power Defense Frame 3 Panelboards, Eaton Pow-R-Line Panelboards
Wire Gauge 250-500 kcmil (Al/Cu)
Max Wire 500 kcmil
Min Wire 250 kcmil
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed Thermal, Adjustable Magnetic
Standards and features
Available Options Auxiliary Switch, Shunt Trip, Undervoltage Release, Alarm Switch, Padlock Attachment
Accessories Standard Line and Load Terminals (PDG3X3TA350)
Standards CSA C22.2 No. 5, IEC 60947-2, UL 489, RoHS Compliant
Approval CCC, CE, CSA, IEC, UL, RoHS
Temp Rating -20C to 70C
Construction Features HACR Rated

Product FAQs

9 answers
What panelboards are compatible with the PDG33M0250TFAJ?

This Frame 3 Power Defense breaker is designed for use in Eaton Power Defense Frame 3 panelboards and Eaton Pow-R-Line panelboards.

What wire sizes are accepted by the lugs on this breaker?

The factory-installed lugs accept 250 to 500 kcmil aluminum or copper wire. Ensure proper torque specifications are followed during installation as outlined in the Eaton Frame 3 instruction leaflet.

How does the trip unit operate on the PDG33M0250TFAJ?

It features a thermal-magnetic trip unit with fixed thermal protection for long-time overloads and adjustable magnetic protection for instantaneous short circuits. The magnetic pickup can be adjusted to coordinate with downstream devices or specific load inrush currents.

Can the PDG33M0250TFAJ replace older Eaton breakers in existing panels?

The Power Defense series is the modern successor to legacy Eaton and Cutler-Hammer lines. Because Frame 3 dimensions and mounting footprints may differ from older models, verify physical space and bus connections in existing enclosures before retrofitting.

Can this breaker be used in DC applications?

Yes, the PDG33M0250TFAJ is rated for up to 250VDC with an interrupting capacity of 22kA. When installing in DC systems, ensure the wiring configuration matches Eaton guidelines for multi-pole DC applications.

What does the M in the PDG33M0250TFAJ catalog number signify?

In the Eaton Power Defense nomenclature, the M indicates the interrupting rating level. For Frame 3, this corresponds to 65kAIC at 480VAC and 100kAIC at 240VAC.

How is the PDG33M0250TFAJ mounted in a panel?

This is a panel-mount breaker that uses a feed-thru connection type. It secures directly to the panelboard chassis using standard mounting hardware for Eaton Frame 3 devices.

Can I add field-installable accessories to this breaker?

Yes, the Power Defense Frame 3 platform supports a variety of field-installable accessories, including shunt trips, undervoltage releases, and auxiliary switches. These install internally without adding to the overall footprint of the breaker.

Does this breaker provide ground fault protection?

No, the PDG33M0250TFAJ features an LI trip unit, which provides long-time and instantaneous protection only. It does not include integral ground fault protection.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.