ABB / General ElectricTED136100
Quantity
New
Quantity
Quantity
New
Quantity
| Brand | ABB / General Electric |
|---|---|
| Part Number | TED134100 |
| Series | TED |
| Amperage | 100A |
| Poles | 3 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480VAC, 600VAC, 250VDC, 500VDC |
| Phase | 3 |
| AIC Rating | 18kA @ 240VAC, 18kA @ 480VAC, 14kA @ 600VAC, 10kA @ 250VDC, 10kA @ 500VDC |
| Terminal Type | Lugs |
|---|---|
| For Use With | GE A-Series Panelboards, Spectra Series Switchboards |
| Wire Gauge | 3 AWG - 3/0 AWG (Cu), 1 AWG - 3/0 AWG (Al) |
| Max Wire | 3/0 AWG |
| Min Wire | 3 AWG (Cu), 1 AWG (Al) |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment |
|---|---|
| Accessories | Load Side Lugs (TCAL15) |
| Standards | CSA C22.2 No. 5.1, HACR, UL 489, NEMA AB 1 |
| Approval | CE, CSA, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Reverse Feed, Non-Interchangeable Trip, Quick-Make/Quick-Break, Trip-Free Mechanism |
Quantity
Re-Certified
Quantity
| Brand | ABB / General Electric |
|---|---|
| Part Number | TED134100-R |
| Series | TED |
| Amperage | 100A |
| Poles | 3 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480VAC, 600VAC, 250VDC, 500VDC |
| Phase | 3 |
| AIC Rating | 18kA @ 240VAC, 18kA @ 480VAC, 14kA @ 600VAC, 10kA @ 250VDC, 10kA @ 500VDC |
| Terminal Type | Lugs |
|---|---|
| For Use With | GE A-Series Panelboards, Spectra Series Switchboards |
| Wire Gauge | 3 AWG - 3/0 AWG (Cu), 1 AWG - 3/0 AWG (Al) |
| Max Wire | 3/0 AWG |
| Min Wire | 3 AWG (Cu), 1 AWG (Al) |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment |
|---|---|
| Accessories | Load Side Lugs (TCAL15) |
| Standards | CSA C22.2 No. 5.1, HACR, UL 489, NEMA AB 1 |
| Approval | CE, CSA, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Reverse Feed, Non-Interchangeable Trip, Quick-Make/Quick-Break, Trip-Free Mechanism |
ABB / General ElectricTED136100
ABB / General ElectricTED136110
ABB / General ElectricTED136090
ABB / General ElectricTED134090
| Brand | ABB / General Electric |
|---|---|
| Part Number | TED134100 |
| Series | TED |
| Amperage | 100A |
| Poles | 3 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480VAC, 600VAC, 250VDC, 500VDC |
| Phase | 3 |
| AIC Rating | 18kA @ 240VAC, 18kA @ 480VAC, 14kA @ 600VAC, 10kA @ 250VDC, 10kA @ 500VDC |
| Terminal Type | Lugs |
|---|---|
| For Use With | GE A-Series Panelboards, Spectra Series Switchboards |
| Wire Gauge | 3 AWG - 3/0 AWG (Cu), 1 AWG - 3/0 AWG (Al) |
| Max Wire | 3/0 AWG |
| Min Wire | 3 AWG (Cu), 1 AWG (Al) |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment |
|---|---|
| Accessories | Load Side Lugs (TCAL15) |
| Standards | CSA C22.2 No. 5.1, HACR, UL 489, NEMA AB 1 |
| Approval | CE, CSA, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Reverse Feed, Non-Interchangeable Trip, Quick-Make/Quick-Break, Trip-Free Mechanism |
This E-frame circuit breaker is engineered for installation in GE A-Series panelboards and Spectra Series switchboards. Depending on the exact enclosure, a separate mounting hardware kit like the TED1DPK may be required to properly secure the breaker to the busbar.
Yes. Like most GE E150 frame breakers, this unit is suitable for reverse feed applications. The thermal magnetic trip mechanism will operate safely regardless of whether the line voltage is connected to the top or bottom terminals.
Yes, it carries a 10kA interrupting capacity at both 250VDC and 500VDC. When utilizing molded case circuit breakers for 500VDC systems, electricians must follow the manufacturer wiring diagrams, which typically require wiring multiple poles in series to safely interrupt the direct current arc.
No, this is a non-interchangeable trip breaker. It is manufactured with fixed thermal and fixed magnetic trip elements calibrated for exactly 100 amps. The entire unit must be swapped if a different amperage or trip curve is required by the circuit.
Yes, ABB continues to support the E150 frame product line. The TED134100 remains an active catalog number and serves as a direct drop-in replacement for older GE TED and TEB series breakers with matching 100A, 3-pole configurations.
Yes, the standard mechanical lugs are dual-rated for copper and aluminum. They accept 1 AWG to 3/0 AWG aluminum wire or 3 AWG to 3/0 AWG copper wire. Electricians should always apply a compatible oxide-inhibiting joint compound when terminating aluminum conductors.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.