ABB / General ElectricTEL136070WL
Quantity
Re-Certified
Quantity
ABB / General ElectricTEL136070WL
ABB / General ElectricTEL134025WL
ABB / General ElectricTEL136020WL
ABB / General ElectricTEL136015WL
| Brand | ABB / General Electric |
|---|---|
| Part Number | TEL136050WL-R |
| Series | TEL |
| Amperage | 50A |
| Poles | 3 |
| Mounting Style | Unit Mount |
| Voltage | 240VAC, 480VAC, 600VAC, 250VDC, 500VDC |
| Phase | 3 |
| AIC Rating | 100kA @ 240VAC, 65kA @ 480VAC, 25kA @ 600VAC, 10kA @ 250VDC, 10kA @ 500VDC |
| Terminal Type | Lugs |
|---|---|
| For Use With | GE A-Series Panelboards, GE Spectra Switchboards, Motor Control Centers |
| Wire Gauge | 14-3 AWG (Cu) or 12-1 AWG (Al) |
| Max Wire | 3 AWG (Cu) / 1 AWG (Al) |
| Min Wire | 14 AWG (Cu) / 12 AWG (Al) |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch |
|---|---|
| Accessories | Line & Load Lugs (TCAL12) |
| Standards | CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489 |
| Approval | CSA, HACR, UL |
| Temp Rating | 40C |
| Construction Features | Current Limiting, HACR Rated, Common Trip, Non-Interchangeable Trip, Trip-Free Mechanism |
| Special Features | Current Limiting |
This E-frame breaker is designed for use in GE A-Series panelboards, GE Spectra switchboards, and compatible motor control centers.
The factory-installed line and load lugs accept 14 to 3 AWG copper wire or 12 to 1 AWG aluminum wire. Ensure proper torque specifications are applied during installation.
This is a unit-mount, feed-thru circuit breaker. It bolts directly to the mounting surface or enclosure backpan and connects via cable, rather than plugging onto a busbar.
Yes, it is rated for DC systems up to 500VDC, providing a 10kA interrupting capacity at both 250VDC and 500VDC. Ensure proper wiring configurations are followed for DC installations.
Yes, the TEL series features a current-limiting design to restrict let-through energy during a short circuit fault, protecting downstream components.
The WL suffix indicates that the breaker comes complete with factory-installed line and load side lug terminals.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.