| Brand | ABB / General Electric |
|---|---|
| Series | TEYD |
| Amperage | 60A |
| Poles | 3 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480Y/277VAC, 250VDC, 120/240VAC |
| Phase | 3 |
| AIC Rating | 65kA @ 240VAC, 25kA @ 480Y/277VAC, 10kA @ 250VDC, 65kA @ 120/240VAC |
| Frame Type | 125A/TEY |
|---|---|
| Terminal Type | Lugs |
| For Use With | GE A-Series Lighting Panelboards |
| Wire Gauge | 10-4 AWG (Cu/Al) |
| Max Wire | 4 AWG |
| Min Wire | 10 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Padlock Attachment, Handle Lock, Mounting Base |
|---|---|
| Accessories | Lugs |
| Standards | CSA C22.2 No. 5, NEMA AB 1, UL 489 |
| Approval | CSA, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Common Trip, Non-Interchangeable Trip, Quick-Make/Quick-Break |
This unit is engineered for bolt-on installation in GE A-Series lighting panelboards, securing directly to the interior bus structure.
No, this breaker is slash-rated for 480Y/277VAC, meaning it is only suitable for solidly grounded wye systems where the voltage to ground does not exceed 277V.
Yes, this model is certified for direct current applications up to 250VDC, offering a 10kA interrupting capacity for DC systems.
The letter D specifies the interrupting rating tier within the Q-Line TEY family. It delivers a 25kA rating at 480Y/277VAC, providing a step up in fault protection compared to the standard 14kA TEY series.
No, this unit utilizes a thermal magnetic trip unit with fixed long-time and fixed instantaneous protection functions. The trip curve is factory calibrated and cannot be altered.
The line side of the breaker bolts directly to the panelboard bus, while the load side features mechanical lugs designed to terminate 10 AWG to 4 AWG copper or aluminum wire.
Yes, the TEYD model shares the identical physical footprint and mounting base as the standard TEY series. It serves as a direct drop-in replacement that provides a higher 25kA interrupting capacity.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.