ABB / General ElectricTEYL2050B
Quantity
New
Quantity
ABB / General ElectricTEYL2050B
ABB / General ElectricTEYL2040B
ABB / General ElectricTEYL2035B
ABB / General ElectricTEYL2060B
| Brand | ABB / General Electric |
|---|---|
| Series | TEYL |
| Amperage | 45A |
| Poles | 2 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480Y/277VAC, 125VDC, 250VDC, 120/240VAC |
| Phase | 1 |
| AIC Rating | 100kA @ 240VAC, 65kA @ 480Y/277VAC, 42kA @ 125VDC, 20kA @ 250VDC, 100kA @ 120/240VAC |
| Frame Type | TEYL |
|---|---|
| Terminal Type | Lugs |
| For Use With | GE A-Series Panelboards |
| Wire Gauge | 10-4 AWG (Cu/Al) |
| Max Wire | 4 AWG |
| Min Wire | 10 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Handle Tie, Padlock Attachment |
|---|---|
| Accessories | Load Lugs |
| Standards | CSA C22.2 No. 5, UL 489 |
| Approval | CSA, HACR, HID, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, HID Rated, Quick-Make/Quick-Break, Common Trip, Non-Interchangeable Trip |
The TEYL2045B is a bolt-on molded case circuit breaker designed specifically for use in GE A-Series panelboards. It requires a 2-inch space (1 inch per pole) and bolts directly to the panel bus.
Yes, this breaker is rated for DC systems. It provides an interrupting capacity of 42kAIC at 125VDC and 20kAIC at 250VDC.
These breakers share the same 1-inch per pole physical footprint for A-Series panelboards but offer different short-circuit interrupting tiers at 480Y/277VAC. The TEYL series provides the highest rating at 65kAIC, compared to TEY (14kA), TEYF (18kA), TEYD (25kA), and TEYH (35kA). The TEYL2045B can safely replace lower-tier models where higher fault protection is required.
The factory-installed lugs accept 10-4 AWG copper or aluminum wire. Recommended tightening torque is 35 in-lb for #10 AWG, 40 in-lb for #8 AWG, and 45 in-lb for #6 to #4 AWG conductors.
Yes, the TEYL2045B is rated for reverse feed. This allows it to be back-fed and used as a main breaker in compatible A-Series panelboards.
No, this breaker utilizes a standard thermal-magnetic trip unit with fixed long-time and fixed instantaneous (LI) trip functions. It is not adjustable.
Yes, TEYL frame circuit breakers are HACR rated, making them suitable for group motor applications like heating, air conditioning, and refrigeration equipment.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.