| Brand | ABB / General Electric |
|---|---|
| Part Number | TEYL2090B |
| Series | TEYL |
| Amperage | 90A |
| Poles | 2 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480Y/277VAC, 125VDC, 250VDC, 120/240VAC |
| Phase | 1 |
| AIC Rating | 100kA @ 240VAC, 65kA @ 480Y/277VAC, 42kA @ 125VDC, 20kA @ 250VDC, 100kA @ 120/240VAC |
| Terminal Type | Lugs |
|---|---|
| For Use With | GE A-Series Panelboards |
| Wire Gauge | 4-1/0 AWG (Cu/Al) |
| Max Wire | 1/0 AWG |
| Min Wire | 4 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Bell Alarm, Padlock Attachment, Handle Lock |
|---|---|
| Accessories | Load Lugs |
| Standards | CSA C22.2 No. 5, UL 489 |
| Approval | CSA, HACR, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Quick-Make/Quick-Break, Common Trip, Trip-Free Mechanism |
This breaker is designed specifically for use in GE A-Series panelboards. It features a bolt-on connection to secure it directly to the panel bus.
No, TEYL series breakers are bolt-on devices designed for commercial and industrial A-Series panelboards. They will not fit into residential plug-on load centers like the Powermark Gold series.
The factory-installed lugs accept wire sizes from 4 AWG up to 1/0 AWG. They are rated for both copper (Cu) and aluminum (Al) conductors.
ABB acquired GE Industrial Solutions in 2018. Depending on the manufacturing date, the TEYL2090B may feature either GE or ABB branding, but the physical dimensions, ratings, and panel compatibility remain identical.
In the GE Q-Line family, the L indicates a high interrupting capacity. The TEYL2090B provides a 65kA interrupting rating at 480/277VAC, which is higher than standard TEY or TEYF versions.
Yes, the TEYL2090B carries DC ratings. It is rated for 42kA at 125VDC and 20kA at 250VDC, making it suitable for specific direct current installations.
No, this thermal-magnetic breaker features fixed long-time and instantaneous (LI) trip functions. The trip points cannot be adjusted in the field.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.