| Brand | ABB / General Electric |
|---|---|
| Part Number | THQL32030ST1 |
| Series | THQL |
| Amperage | 30A |
| Poles | 3 |
| Mounting Style | Plug-On |
| Voltage | 240VAC |
| Phase | 3 |
| AIC Rating | 10kA @ 240VAC |
| Frame Type | THQL |
|---|---|
| Terminal Type | Box Lugs |
| For Use With | GE PowerMark Gold Load Centers, GE AQ Lighting Panels |
| Wire Gauge | 14-8 AWG (Cu), 12-8 AWG (Al) |
| Max Wire | 8 AWG |
| Min Wire | 14 AWG (Cu), 12 AWG (Al) |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed |
| Available Options | Padlock Attachment, Auxiliary Switch |
|---|---|
| Accessories | Shunt Trip (Factory Installed) |
| Standards | HACR, NEMA AB 1, UL 489 |
| Approval | CSA, UL |
| Temp Rating | 60C to 75C |
| Construction Features | HACR Rated, Common Trip, Quick-Make/Quick-Break |
The ST1 suffix indicates that the breaker includes a factory-installed 120VAC shunt trip accessory. This allows the breaker to be opened remotely via an external control signal.
The THQL32030ST1 is a plug-on breaker designed for load centers, while the THQB32030ST1 is a bolt-on breaker typically used in commercial panelboards. Both share the same 30A rating, 3-pole configuration, and 120V shunt trip accessory.
Yes, this breaker is compatible with GE AQ Lighting Panels as well as residential GE PowerMark Gold Load Centers, provided the specific panel interior accepts plug-on THQL frame breakers.
Yes, the 120VAC shunt trip mechanism requires an external 120V control voltage to actuate the trip coil. When voltage is applied to the shunt trip leads, the breaker will open.
The shunt trip is typically used for emergency shutdown systems. It allows the breaker to be tied into fire alarm panels, emergency stop push buttons, or equipment safety interlocks that require a rapid remote power disconnection.
Yes, the box lugs on this breaker are rated for both copper and aluminum conductors. The terminals accept 14 to 8 AWG copper wire or 12 to 8 AWG aluminum wire.
No, the THQL32030ST1 is a standard thermal-magnetic breaker providing long-time and instantaneous trip functions for overload and short-circuit protection. It does not include GFCI or AFCI capabilities.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.