Built to handle demanding commercial and marine environments, this 3-pole 20A breaker utilizes a TM210 thermal-magnetic trip unit with fixed settings. The Siemens 3VA5120-6ED31-0AA0 mounts into P2, P3, P4, and P5 panelboards or switchboards when equipped with the proper hardware. It serves as a modern replacement for legacy HHED63B020 breakers. With a 65kAIC rating at 480VAC and current-limiting capabilities, it ensures superior protection against overloads and short circuits.
HACR Rated, Current Limiting, Reverse Feed, Trip-Free Mechanism, High Interrupting Capacity
Product FAQs
9 answers
What legacy Siemens breaker does the 3VA5120-6ED31-0AA0 replace?
This 3VA5 series breaker serves as a modern replacement for legacy HHED63B020 circuit breakers.
Is the 3VA5120-6ED31-0AA0 rated for reverse feed applications?
Yes, Siemens 3VA5 thermal-magnetic trip circuit breakers are UL listed for reverse feed applications.
Can this breaker be used in direct current (DC) systems?
Yes, the 3VA5120-6ED31-0AA0 is rated for DC applications up to 500VDC with an interrupting capacity of 100kA.
How should the 3-pole 3VA5120-6ED31-0AA0 be wired for 500VDC applications?
For 500VDC systems, two poles must be connected in series on one leg of the supply circuit, with the third pole connected on the opposite leg.
Which Siemens panelboards are compatible with this breaker?
The 3VA5120-6ED31-0AA0 is designed for installation in Siemens P2, P3, P4, and P5 panelboards, as well as compatible switchboards and enclosures.
Is the 3VA5120-6ED31-0AA0 a current-limiting circuit breaker?
Yes, this breaker features current-limiting capabilities to provide enhanced protection against overloads and short circuits.
Is this breaker HACR rated?
Yes, the 3VA5120-6ED31-0AA0 is HACR rated, making it suitable for heating, air conditioning, and refrigeration equipment circuits.
What type of trip unit is installed in the 3VA5120-6ED31-0AA0?
This breaker utilizes a TM210 thermal-magnetic trip unit with fixed thermal and fixed magnetic settings for long-time and instantaneous (LI) protection.
What is the frame size of the 3VA5120-6ED31-0AA0?
This breaker is built on the Siemens 3VA51 frame, which has a maximum rating of 125 amps.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 4.8 out of 5 based on 8 reviews.