Belonging to the advanced SENTRON series, this 2-pole, 30A MCCB provides reliable power distribution for industrial environments. The breaker mounts into Siemens P1, P2, and P3 panelboards. Facility managers can utilize this unit to replace older ED62B030 and ED42B030 breakers without extensive panel modifications. It utilizes a TM210 trip unit for fixed thermal and magnetic (LI) protection. With a 65kA rating at 240V, this current-limiting device effectively isolates electrical faults.
Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Motor Operator, Rotary Handle, Padlock Attachment, Lug Kits, DIN Rail Adapter
Accessories
None (Standard)
Standards
CSA C22.2 No. 5, IEC 60947-2, UL 489
Approval
CCC, CE, CSA, EAC, IEC, UL, VDE
Temp Rating
-25C to 70C
Construction Features
HACR Rated, Current Limiting, Reverse Feed, Trip-Free Mechanism
Product FAQs
6 answers
Which legacy Siemens breakers can the 3VA5130-4ED21-0AA0 replace?
This 3VA5 series breaker functions as a direct replacement for older ED42B030 and ED62B030 30A, 2-pole circuit breakers. It upgrades legacy systems without requiring extensive panel modifications.
Which Siemens panelboards accept the 3VA5130-4ED21-0AA0 circuit breaker?
This panel mount breaker is engineered specifically for installation in Siemens P1, P2, and P3 panelboards, as well as compatible Siemens switchboards.
Can the trip curve be adjusted on this 30A SENTRON breaker?
No, this unit is equipped with a thermal-magnetic trip unit that features fixed long-time and fixed instantaneous (LI) protection. The thermal and magnetic trip points cannot be adjusted in the field.
Is this 2-pole breaker rated for direct current applications?
Yes, in addition to its AC ratings, this breaker is rated for use in DC systems with an interrupting capacity of 50kA at 250VDC.
What frame size does the 3VA5130-4ED21-0AA0 belong to?
This breaker is built on the Siemens 3VA51 UL 125A frame platform. While the physical frame supports up to 125 amps, this specific unit is factory-configured for a maximum continuous current of 30 amps.
What is the breaking capacity class for this specific 3VA5 breaker?
The number 4 in the part number designates this as a Class S breaker, which provides a standard breaking capacity of 25kA at 480V and 65kA at 240V.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 4.8 out of 5 based on 8 reviews.