Siemens NGB2B030B Molded Case Circuit Breaker

  • 30A
  • 2 Pole
  • Bolt-On
Siemens NGB2B030B
Molded Case Circuit Breaker
Brand Siemens
SKU NGB2B030B
Select Item Condition
Earn 252 SuperPoints
  • 30A
  • 2 Pole
  • Bolt-On

Quantity

Bulk Pricing
Send your parts list for a volume quote.
Siemens NGB2B030B - 30A 2 Pole Molded Case Circuit Breaker

Siemens NGB2B030B - 30A 2 Pole Molded Case Circuit Breaker

New

$252.49 In Stock

Quantity

Similar Items

Description

Engineered for commercial power distribution, this 30-amp, 2-pole SENTRON MCCB provides reliable thermal-magnetic protection. It is built to handle demanding industrial environments. Designed for bolt-on installation, the NGB2B030B mounts into Siemens P1, P2, and P3 panelboards. It supports legacy GB/GG frame applications and is eventually replaced by the 3VA51 series. Rated 100kAIC at 240V, this breaker is HACR and HID rated, supports reverse feed, and includes load side lugs.

Specifications

Key specifications
Brand Siemens
Part Number NGB2B030B
Series NGB
Amperage 30A
Poles 2
Mounting Style Bolt-On
Voltage 240VAC, 480Y/277VAC, 600Y/347VAC, 125/250VDC
Phase 1
AIC Rating 100kA @ 240VAC, 25kA @ 480Y/277VAC, 14kA @ 600Y/347VAC, 14kA @ 125/250VDC
Fit and installation
Frame Type NGB
Terminal Type Lugs
For Use With Siemens P1, P2, P3 Panelboards
Wire Gauge 14-6 AWG (Cu), 12-6 AWG (Al)
Max Wire 6 AWG
Min Wire 14 AWG (Cu), 12 AWG (Al)
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed Thermal, Fixed Magnetic
Standards and features
Available Options Shunt Trip, Auxiliary Switch, Alarm Switch
Accessories Load Side Lugs
Standards CSA C22.2 No. 5, UL 489, NEMA AB 1
Approval CSA, HACR, HID, UL
Temp Rating 40C
Construction Features HACR Rated, Reverse Feed

Product FAQs

7 answers
Which panelboards are compatible with the NGB2B030B circuit breaker?

This bolt-on breaker is specifically designed for installation in Siemens P1, P2, and P3 commercial panelboards. It is not compatible with standard residential load centers.

What wire sizes and materials are accepted by the load lugs?

The factory-installed lugs accept 14 to 6 AWG copper (Cu) wire or 12 to 6 AWG aluminum (Al) wire.

Can the NGB2B030B be used in direct current (DC) applications?

Yes, in addition to its AC ratings, this thermal-magnetic breaker is rated for 125/250VDC systems, providing up to 14kAIC of interrupting capacity.

Does this breaker feature adjustable trip settings?

No, the NGB2B030B utilizes a fixed thermal and fixed magnetic trip unit. The long-time and instantaneous (LI) trip thresholds cannot be adjusted in the field.

Is the NGB2B030B a direct replacement for older GB or GG frame breakers?

Yes, the NGB frame is part of the Siemens Sentron family and is designed to support legacy GB and GG frame applications in existing panelboards.

Does this breaker provide ground-fault or arc-fault protection?

No, this is a standard thermal-magnetic breaker designed for overcurrent and short-circuit protection. It does not include GFCI, AFCI, or GFEP safety circuitry.

Is the NGB2B030B suitable for reverse feed applications?

Yes, this thermal-magnetic breaker supports reverse feed wiring configurations, allowing it to be back-fed in commercial power distribution setups.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.