Siemens NGB2B110B - 110A 2 Pole Molded Case Circuit Breaker

Siemens NGB2B110B - 110A 2 Pole Molded Case Circuit Breaker

New

$552.88 In Stock

Quantity

Similar Items

Description

Engineered for commercial power distribution, the Siemens NGB2B110B is a 2-pole, 110A molded case circuit breaker featuring fixed thermal-magnetic trip units for dependable LI protection. This bolt-on MCCB mounts into Siemens P1, P2, and P3 panelboards. For legacy system upgrades, it is replaced by the 3VA5111-4ED21-0AA0, which requires a strap kit for proper installation. Rated at 100kAIC at 240VAC, this HACR-rated breaker supports reverse feed applications and accepts 8-1/0 AWG copper wire.

Specifications

Key specifications
Brand Siemens
Series NGB
Amperage 110A
Poles 2
Mounting Style Bolt-On
Voltage 240VAC, 480Y/277VAC, 600Y/347VAC, 125/250VDC
Phase 1
AIC Rating 100kA @ 240VAC, 25kA @ 480Y/277VAC, 14kA @ 600Y/347VAC, 14kA @ 125/250VDC
Fit and installation
Frame Type NGB
Terminal Type Lugs
For Use With Siemens P1, P2, P3 Panelboards
Wire Gauge 8-1/0 AWG (Cu), 8-2/0 AWG (Al)
Max Wire 1/0 AWG (Cu), 2/0 AWG (Al)
Min Wire 8 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed Thermal, Fixed Magnetic
Standards and features
Available Options Shunt Trip, Auxiliary Switch, Alarm Switch
Accessories Load Lugs
Standards CSA C22.2 No. 5, IEC 60947-2, UL 489
Approval CSA, HACR, UL
Temp Rating 40C
Construction Features HACR Rated, Reverse Feed

Product FAQs

6 answers
Which Siemens panelboards are compatible with the NGB2B110B?

This bolt-on breaker is designed for use in Siemens P1, P2, and P3 lighting and distribution panelboards. It mounts directly to the panelboard bus structure.

What wire sizes are accepted by the factory lugs on this breaker?

The standard lugs accept 8 AWG to 1/0 AWG copper conductors or 8 AWG to 2/0 AWG aluminum conductors. Always apply the specific torque value printed on the breaker faceplate during installation.

Is the NGB2B110B rated for direct current (DC) systems?

Yes, this breaker is rated for DC applications up to 125/250VDC with an interrupting capacity of 14kAIC, making it suitable for specific industrial control or battery backup circuits.

How does the NGB frame compare to HGB or LGB breakers?

The NGB, HGB, and LGB series share the exact same physical footprint and panelboard compatibility. They differ only in interrupting ratings. The NGB is the standard interrupting tier, while HGB and LGB offer higher fault current ratings for systems with higher available fault currents.

Can the trip settings on the NGB2B110B be adjusted in the field?

No, this breaker features a thermal magnetic trip unit with fixed long-time and fixed instantaneous trip functions. It does not have field-adjustable dials.

Can this breaker be used as a back-fed main breaker?

Yes, it can be used as a main or branch breaker depending on the panelboard configuration. When installed as a back-fed main, a dedicated hold-down kit is required to comply with National Electrical Code (NEC) standards.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.