Serving industrial applications, this 30A PowerPacT B-frame breaker delivers reliable long-time and instantaneous (LI) trip functions. The unit integrates into Square D I-Line panelboards using a factory-configured AC phase connection. Facility managers can use this model to replace the discontinued FA26030AC. With a 65kAIC interrupt rating at 240V, it offers robust current-limiting performance. The reverse-feed capability and push-to-trip mechanism simplify testing.
CSA C22.2 No 5, EN/IEC 60947-2, EN/IEC 60947-5-1, GB 14048.2, NEMA AB 1, NMX J-266, UL 489
Approval
CCC, CE, CSA, EAC, IEC, NOM, UL
Temp Rating
-25C to 70C
Construction Features
HACR Rated, Reverse Feed
Product FAQs
7 answers
Does the BGA260302 replace older Square D I-Line circuit breakers?
Yes, this PowerPacT B-frame breaker is the direct replacement for discontinued FA and FH frame models. Specifically, it replaces the FA26030AC and FH26030AC.
What type of panelboards are compatible with the BGA260302?
This breaker is designed exclusively for use in Square D I-Line panelboards and switchboards. It features an I-Line plug-in mounting style that stabs directly into the bus assembly.
What phase connection does the BGA260302 have for I-Line panelboards?
This specific catalog number features a factory-configured AC phase connection, which is indicated by the 2 at the end of the part number.
What wire sizes are accepted by the lugs on this 30A breaker?
The load-side mechanical lugs accept wire gauges from 14 AWG up to 2/0 AWG. They are rated for use with both aluminum and copper conductors.
How does the I-Line mounting system work on the BGA260302?
The I-Line design features a plug-in connection on the line side that snaps directly onto the panelboard bus. This eliminates the need for line-side wire connections and speeds up installation compared to traditional bolt-on breakers.
What does the G in the BGA260302 catalog number indicate?
In the PowerPacT B-frame series, the G designates the interrupting rating tier. For this model, it signifies an interrupting capacity of 65kA at 240VAC, 35kA at 480VAC, and 18kA at 600VAC.
Can this 2-pole breaker be used in DC applications?
Yes, the BGA260302 is rated for DC systems up to 250VDC, providing an interrupting capacity of 20kAIC.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.