Built for heavy-duty industrial applications, this 35A PowerPacT B-Frame MCCB provides fixed long-time and instantaneous trip functions. It offers reliable overcurrent defense for 480Y/277VAC commercial systems. The unit mounts into Square D I-Line panelboards and switchboards via an ABC phase connection. It serves as an exact replacement for the legacy FA34035 breaker. Rated to interrupt 35 kAIC at 480Y/277VAC, the BGA34035Y includes a Visi-Trip indicator and carries an HACR rating.
Can I use the BGA34035Y to replace an older FA34035 breaker?
Yes. The PowerPacT B-Frame series is the designated replacement for legacy Square D F-Frame circuit breakers. The BGA34035Y serves as a direct, exact replacement for the obsolete FA34035 in I-Line panelboards.
What are the magnetic hold and trip current settings for this 35A breaker?
The BGA34035Y features a fixed magnetic trip unit with a short-circuit hold current of 400A and a short-circuit trip current of 600A.
Is the BGA34035Y rated for DC applications?
Yes, this thermal-magnetic breaker is dual-rated for both AC and DC operation. It supports DC systems up to 250VDC with a maximum interrupting rating of 20kA.
What wire sizes are accepted by the load-side lugs?
The factory-installed mechanical lugs accept aluminum or copper conductors ranging from 14 AWG to 2/0 AWG.
How does this breaker connect to the panelboard?
The BGA34035Y features an I-Line style plug-in connection on the line side. It stabs directly onto the busbar of compatible Square D I-Line panelboards and switchboards using a standard ABC phase connection, while the load side utilizes mechanical lugs.
Are the trip settings adjustable on the BGA34035Y?
No. This breaker is equipped with a fixed thermal-magnetic trip unit. Both the long-time (overload) and instantaneous (short-circuit) trip functions are non-interchangeable and non-adjustable.
Is this breaker suitable for HVAC equipment?
Yes, the BGA34035Y carries an HACR rating, making it approved for use with heating, air conditioning, and refrigeration equipment that requires this specific certification.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 4.9 out of 5 based on 7 reviews.