Engineered for industrial power distribution, the Square D BGA34125Y is a 3-pole, 125A molded case circuit breaker. It is part of the PowerPacT B-Frame series, offering compact thermal-magnetic protection. This breaker mounts into standard Square D I-Line panelboards and switchboards. It is an ideal modern substitute for the discontinued FA34125, maintaining the same 1.5-inch per pole width. With a 35kAIC rating at 480Y/277V, this HACR-rated breaker features a push-to-trip mechanism.
CSA C22.2 No 5, EN/IEC 60947-2, EN/IEC 60947-5-1, GB 14048.2, NEMA AB 1, NMX J-266, UL 489
Approval
CCC, CE, CSA, EAC, IEC, NOM, UL
Temp Rating
-25C to 70C
Construction Features
HACR Rated, Reverse Feed
Product FAQs
6 answers
What panels are compatible with the BGA34125Y and how does it mount?
This breaker is designed exclusively for Square D I-Line panelboards and switchboards. It mounts using the standard I-Line system, featuring plug-on jaws that connect directly to the bus assembly and a screw-on retaining bracket for secure installation.
Can the BGA34125Y be used to replace an older FA34125 breaker?
Yes, the PowerPacT B-Frame series is the direct modern replacement for discontinued Square D F-Frame breakers, including the FA34125. It maintains the same 1.5-inch per pole width and mounts onto the same I-Line bus.
What does the 'G' in the BGA34125Y catalog number indicate?
The 'G' designates the breaker's interrupting rating tier. In the PowerPacT B-Frame series, a 'G' rating provides 65kA at 240VAC, 35kA at 480VAC, and 20kA at 250VDC.
Does the BGA34125Y come with factory-installed lugs?
Yes, it includes standard mechanical lugs on the load side that accept 14 AWG to 2/0 AWG aluminum or copper wire. The line side connects directly to the I-Line bus.
How does the thermal-magnetic trip unit operate on the BGA34125Y?
The breaker uses a fixed thermal-magnetic trip unit providing Long-Time (L) protection for overloads and Instantaneous (I) protection for short circuits. These settings are factory-calibrated and non-adjustable.
Is the BGA34125Y suitable for DC voltage applications?
Yes, this breaker is rated for DC applications up to 250VDC, providing a maximum interrupting capacity of 20kA.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 4.9 out of 5 based on 7 reviews.