Built for heavy-duty industrial use, this 2-pole, 30A PowerPacT B-frame circuit breaker offers superior thermal-magnetic protection. The BJA260304 handles demanding loads safely. Equipped with a phase BC connection, it integrates smoothly into Square D I-Line panelboards. It can also be used to replace obsolete FH26030BC breakers. The unit boasts a 65kAIC rating at 480VAC and features fixed long-time and instantaneous (LI) trip settings. It includes a Visi-Trip indicator.
HACR Rated, Current Limiting, Visual Trip Indicator
Product FAQs
8 answers
What panels are compatible with the BJA260304 circuit breaker?
This breaker is designed exclusively for Square D I-Line panelboards and switchboards. It features an I-Line style plug-on connection on the line side and mechanical lugs on the load side.
What does the 4 at the end of the BJA260304 catalog number indicate?
The 4 suffix indicates that this 2-pole breaker is configured for a BC phase connection within the I-Line panelboard. If you need a different phase configuration, you will need a different suffix, such as 1 for AB or 2 for AC.
Can the BJA260304 replace older Square D FA or FH series breakers?
Yes, the PowerPacT B-frame is the direct manufacturer replacement for legacy F-frame breakers. The BJA260304 can be used to replace obsolete FA26030BC and FH26030BC circuit breakers while maintaining the exact same mounting space in your existing panel.
What wire sizes do the lugs on the BJA260304 accept?
The factory-installed load lugs accept 14 AWG to 2/0 AWG aluminum or copper wire.
How does the I-Line mounting system work on this breaker?
The breaker features a plug-on line-side connection that snaps directly onto the panelboard busbar for a secure, tool-free line connection. The load side utilizes standard mechanical lugs for wire termination.
What does the J in the BJA260304 part number represent?
The J designates the interrupting rating tier for this PowerPacT B-frame breaker. It provides a high interrupting capacity of 100kA at 240VAC, 65kA at 480VAC, and 25kA at 600Y/347VAC.
Are the trip settings on the BJA260304 adjustable?
No, this breaker features a fixed thermal-magnetic trip unit. Both the long-time (thermal overload) and instantaneous (magnetic short-circuit) protection functions are factory-set and non-adjustable.
Does the BJA260304 include a visual trip indicator?
Yes, it features a Visi-Trip indicator that provides clear visual confirmation when the breaker has tripped. It also includes a push-to-trip button on the cover to manually test the tripping mechanism.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 4.3 out of 5 based on 3 reviews.