Built for robust power distribution, the Square D BJA260704 is a 70A, 2-pole molded case circuit breaker within the PowerPacT B-Frame series. It is designed to handle demanding commercial and industrial electrical loads. Featuring a plug-on I-Line mounting style with a BC phase connection, this unit installs into Square D panelboards and switchboards. It replaces the older FH26070BC model. The breaker delivers a 65kAIC rating at 480V and includes fixed thermal-magnetic trip functions.
CSA C22.2 No 5, EN/IEC 60947-2, GB 14048.2, NEMA AB 1, NMX J-266, UL 489
Approval
CCC, CE, CSA, EAC, IEC, NOM, UL
Temp Rating
-25C to 70C
Construction Features
HACR Rated, Current Limiting, Non-Interchangeable Trip, Reverse Feed, 80% Rated
Product FAQs
7 answers
What legacy Square D circuit breaker does the BJA260704 replace?
The PowerPacT B-frame BJA260704 is the modern replacement for the legacy F-frame FH26070BC circuit breaker. It maintains the same I-Line mounting space dimensions to easily retrofit into existing panels.
What phase connection does the BJA260704 use?
The 4 at the end of the BJA260704 catalog number indicates it is configured for a BC phase connection in I-Line panelboards.
What does the J in the BJA260704 catalog number signify?
The J designates the interrupting rating class. For this PowerPacT B-frame breaker, the J-class provides a 65kA interrupting rating at 480/277VAC and a 100kA rating at 240VAC.
Are the trip settings adjustable on the BJA260704?
No, this breaker features a fixed thermal and fixed magnetic trip unit. The long-time and instantaneous trip points are factory-calibrated and cannot be adjusted in the field.
How does the BJA260704 mount into a panel?
This breaker features an I-Line style plug-in mounting design. It stabs directly into the busbar of compatible Square D I-Line panelboards and switchboards, allowing for quick installation without the need for bolt-on connections.
What internal contact design does the BJA260704 use?
Like all PowerPacT B-frame breakers, it is equipped with dual-break rotating contacts. This design reduces the amount of peak current during a short circuit fault, lowering let-through currents and enhancing equipment protection.
Can the BJA260704 be used in DC applications?
Yes, this thermal-magnetic circuit breaker is rated for DC systems, providing a 50kA interrupting rating at 250VDC.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.