Built for industrial power distribution, this 30A thermal-magnetic breaker delivers reliable LI protection and is factory-configured for AC phase connections. Integration into Square D I-Line panelboards and switchboards is streamlined via the specialized mounting bracket. Facility managers can utilize this to replace discontinued FA26030AC units. Rated to interrupt 25kA at 240VAC, the HACR-approved device ensures robust fault clearing and features an integrated Visi-Trip mechanism.
This PowerPacT H-frame breaker is designed exclusively for Square D I-Line panelboards and switchboards. It utilizes an I-Line plug-in connection for phase mounting.
Can I use this breaker in a standard QO or Homeline load center?
No. The HDA260302 is a PowerPacT H-frame breaker with an I-Line plug-in mounting style. It is strictly designed for commercial and industrial Square D I-Line panelboards and switchboards, not residential QO or Homeline load centers.
How is the HDA260302 mounted in a panel?
The HDA260302 utilizes an I-Line style plug-in connection for the line side, allowing it to snap directly into the bus of compatible Square D panelboards. The load side features standard mechanical lugs.
What wire sizes and materials are supported by the load lugs?
The factory-installed lugs on this breaker accept either aluminum or copper conductors ranging from 14 AWG to 3/0 AWG.
What trip functions does the HDA260302 provide?
This breaker is equipped with a fixed thermal-magnetic trip unit that provides Long-Time (L) and Instantaneous (I) protection against overloads and short circuits.
Is the HDA260302 suitable for systems with high available fault current?
It carries a standard 'D' interrupting rating, providing up to 25kAIC at 240VAC, 18kAIC at 480VAC, and 14kAIC at 600VAC. You must verify that your system's available fault current does not exceed these limits.
Can this breaker be used in DC applications?
Yes, the HDA260302 is rated for DC applications up to 250VDC, providing an interrupting capacity of 20kA at that voltage.
What does the HDA prefix indicate in the PowerPacT series?
In the Square D PowerPacT nomenclature, 'HDA' designates an H-frame breaker with a 'D' interrupting rating (18kA at 480VAC) and an I-Line plug-in mounting configuration.
Can the HDA260302 replace older F-frame breakers?
Yes. The Square D PowerPacT H-frame series is the modern replacement for legacy F-frame breakers. The HDA260302 can be used to replace older 30A, 2-pole FA-series I-Line breakers in Square D panelboards.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 11 reviews.