An exact replacement for discontinued KAL36110 K-Frame units, the Square D HDL36110 is a 3-pole, 110A molded case circuit breaker from the modern PowerPacT H-Frame series. It provides essential long-time and instantaneous (LI) thermal-magnetic protection for commercial and industrial electrical systems. Designed for unit-mount configurations, it easily integrates into industrial control panels and enclosures. The breaker delivers a 25kAIC interrupting rating at 240VAC and 14kAIC at 600VAC.
How does the HDL36110 mount into an electrical enclosure?
This model features a unit-mount design with mechanical lugs on both the line and load sides. It installs by securing it directly to a backpan or mounting plate using screws, rather than plugging onto a bus system.
Is the HDL36110 compatible with I-Line panelboards?
No. The HDL36110 is a unit-mount circuit breaker. To install a 110A PowerPacT H-Frame breaker into an I-Line panelboard, you will need the I-Line version, which typically uses the HDA or HGA prefix.
What are the torque specifications for the wire lugs on the HDL36110?
The standard AL150HD lugs accept both copper and aluminum wire. For 14 to 10 AWG wire, torque the binding screw to 50 lb-in (5 N.m). For 8 to 3/0 AWG wire, torque to 120 lb-in (14 N.m). Always verify torque values against the printed manufacturer label prior to installation.
Does the HDL36110 have adjustable thermal and magnetic trip settings?
No. This breaker is equipped with a thermal-magnetic trip unit that has fixed thermal and fixed magnetic trip settings. If your application requires adjustable trip settings, you must upgrade to a PowerPacT H-Frame model equipped with a MicroLogic electronic trip unit.
What does the letter "D" signify in the HDL36110 part number?
The "D" in the catalog number indicates the breaker's interrupting rating performance level. For the PowerPacT H-Frame series, the "D" tier designates an interrupting capacity of 25kA at 240VAC, 18kA at 480VAC, and 14kA at 600VAC.
Can the HDL36110 replace an older Square D F-Frame breaker?
Yes. The PowerPacT H-Frame series serves as a modern upgrade and designated replacement for legacy Square D F-Frame breakers, such as the FA or FH models, offering higher performance and a wider range of field-installable accessories.
How do you reset the HDL36110 after it trips?
When the breaker trips due to an overcurrent or short circuit, the operating handle moves to a center position between ON and OFF. To restore power, you must first pull the handle completely to the OFF position to reset the internal toggle mechanism, and then push it back to the ON position.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 4.0 out of 5 based on 1 review.