Belonging to the PowerPacT P-Frame family, this 1200A molded case circuit breaker delivers robust power distribution for industrial environments. It features a Micrologic 6.0 A electronic trip unit, offering highly configurable LSIG parameters. The unit-mount configuration integrates into standard switchboards and motor control centers. It also functions as an upgrade path for discontinued NAL361200 units. Rated for 35kA at 480VAC, it includes an integrated ammeter and true RMS sensing.
HACR Rated, 80% Rated, True RMS Sensing, Interchangeable Trip Unit
Product FAQs
9 answers
What specific trip unit is included with the PGL36120U44A?
This breaker is equipped with a Micrologic 6.0A electronic trip unit [1.1.1]. It provides Long-Time, Short-Time, Instantaneous, and Ground-Fault (LSIG) protection, along with an integrated ammeter for current monitoring.
What is the difference between the PGL36120U44A and the PGA36120U44A?
The mounting style is the key difference. The PGL suffix indicates a unit-mount configuration with feed-thru lugs on both ends. The PGA suffix designates an I-Line plug-on configuration designed specifically for Square D I-Line panelboards and switchboards.
What wire sizes are accepted by the factory lugs on this 1200A breaker?
The standard factory feed-thru lugs accept four 3/0 AWG to 500 kcmil aluminum or copper conductors per phase. Always follow the manufacturer torque specifications printed on the breaker label during installation.
Is the PGL36120U44A rated for 80 percent or 100 percent continuous current?
This standard breaker is rated for 80 percent continuous current. If your application requires a 100 percent continuous current rating, you must specify a version with a C suffix in the catalog number, such as PGL36120CU44A.
Can I use this 3-pole breaker for ground fault protection on a 4-wire system?
Yes. The included Micrologic trip unit has built-in ground-fault capabilities. However, when installed in a 3-phase, 4-wire system, a separate external neutral current transformer (CT) must be properly wired to the trip unit to accurately monitor residual ground faults.
Can the continuous current rating be lowered in the field?
Yes. The Micrologic trip unit utilizes interchangeable rating plugs. By installing a lower-value rating plug, a licensed electrician can reduce the maximum long-time pickup setting without having to replace the entire circuit breaker frame.
What does the G represent in the PGL catalog number?
The G indicates the interrupting rating tier within the Square D PowerPacT P-frame family. It signifies a short-circuit interrupting capacity of 35kA at 480VAC and 65kA at 240VAC.
Are the trip settings adjustable on this breaker?
Yes. The Micrologic 6.0A trip unit features adjustable dials for Long-Time, Short-Time, Instantaneous, and Ground-Fault pickup and delay settings. This allows panel builders to precisely coordinate the breaker with upstream and downstream electrical devices.
Does the electronic trip unit require external power to operate?
No. The Micrologic trip unit is internally powered by the current flowing through the phase conductors. An optional external 24 Vdc power supply is only necessary to operate the digital display when the active load current falls below 20 percent of the continuous current rating.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.