Part of the Quicklag family, the Eaton QB1030GF provides 30A of continuous power while actively monitoring for ground faults. It is designed to protect personnel in commercial, industrial, and marine environments where moisture is present. Engineered for bolt-on installation, it fits securely into Eaton Pow-R-Line panelboards. This model replaces the older QBGF1030. Equipped with a pigtail neutral and automated self-testing, the breaker ensures ongoing NEC compliance with a 10kAIC rating.
Can I use the Eaton QB1030GF to replace older Cutler-Hammer breakers?
Yes, Eaton acquired Cutler-Hammer, and the current QB1030GF is an exact, direct replacement for legacy Cutler-Hammer and Westinghouse units with the same specs. It also directly replaces the older legacy catalog number QBGF1030.
What types of electrical panels accept the QB1030GF circuit breaker?
This bolt-on miniature breaker is specifically designed for Eaton Pow-R-Line panelboards and other commercial enclosures that accept BAB or QB-frame bolt-on breakers. It cannot be installed in standard plug-on residential loadcenters like the Eaton BR or CH series.
Does the QB1030GF provide 5mA personnel protection or 30mA equipment protection?
The "GF" suffix in the catalog number designates this as a Class A Ground Fault Circuit Interrupter (GFCI) with a 5mA trip threshold, which is required for personnel protection. Eaton uses an "EP" suffix for its 30mA Ground Fault Equipment Protectors (GFEP).
How must the neutral be wired for this breaker to function correctly?
Because this is a pigtail-style GFCI breaker, you must land the coiled white pigtail wire directly onto the panel's neutral bus bar. The load neutral wire then connects to the neutral terminal on the breaker itself to allow the internal current transformer to monitor for ground faults.
Are the box lug terminals rated for both copper and aluminum wiring?
Yes, the terminals accept both copper (Cu) and aluminum (Al) conductors within the 14 AWG to 4 AWG size range. When terminating aluminum wiring, an approved oxide inhibitor should be applied to the stripped conductor.
Can this 1-pole GFCI breaker be used on a multi-wire branch circuit with a shared neutral?
No. Single-pole GFCI breakers like the QB1030GF monitor the current imbalance between their specific ungrounded load conductor and the load neutral. Using a shared neutral across two phases will immediately cause nuisance tripping. A 2-pole GFCI breaker is required for multi-wire branch circuits.
Does this breaker provide combination arc fault (AFCI) protection?
No. The QB1030GF only provides thermal-magnetic overcurrent and ground fault (GFCI) protection. If your application requires AFCI or dual-function (AFCI/GFCI) protection, a different breaker model with an "AF" or "DF" suffix is required.
How often should the integrated GFCI mechanism be tested?
Safety standards and manufacturer guidelines require pressing the integrated "TEST" button on the face of the breaker monthly to ensure the ground fault circuitry is operating correctly and mechanically trips the breaker.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 1 review.