ABB / General ElectricTHQL1115AF
Quantity
New
Quantity
ABB / General ElectricTHQL1115AF
ABB / General ElectricTHQL1115AF2
ABB / General ElectricTHQL1115PAF2
| Brand | ABB / General Electric |
|---|---|
| Part Number | THQL2115AF |
| Series | THQL |
| Amperage | 15A |
| Poles | 2 |
| Mounting Style | Plug-On |
| Voltage | 120/240VAC |
| Phase | 1 |
| AIC Rating | 10kA @ 120/240VAC |
| Frame Type | THQL |
|---|---|
| Terminal Type | Box Lugs |
| For Use With | GE Q-Line Load Centers, PowerMark Gold Load Centers |
| Wire Gauge | 14-8 AWG (Cu), 12-8 AWG (Al) |
| Max Wire | 8 AWG |
| Min Wire | 14 AWG (Cu), 12 AWG (Al) |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed |
| Special Classification | AFCI |
|---|---|
| Available Options | Shunt Trip, Auxiliary Switch |
| Standards | HACR, NEMA AB 1, UL 1699, UL 489 |
| Approval | CSA, UL |
| Temp Rating | 60C to 75C |
| Construction Features | HACR Rated, Common Trip, Quick-Make/Quick-Break |
This plug-on breaker is designed for use in GE Q-Line and PowerMark Gold load centers. It requires two standard 1-inch spaces for installation.
The THQL2115AF is an older branch/feeder AFCI. The THQL2115AF2 is the newer combination-type AFCI (CAFCI) that meets updated National Electrical Code (NEC) requirements for detecting both parallel and series arcing.
The THQL2115AF features a pigtail neutral connection. The coiled white pigtail wire must be connected directly to the panel neutral bus bar to power the internal arc fault circuitry.
Yes, 2-pole AFCI breakers like the THQL2115AF are commonly used to provide arc fault protection for multi-wire branch circuits that share a single neutral conductor, as well as for dedicated 240V loads.
Yes. While it is not a plug-on neutral breaker, you can still install it in a PON panel by manually wiring the attached neutral pigtail to the neutral bus bar.
No, this unit is strictly an Arc Fault Circuit Interrupter (AFCI). If your application requires both arc fault and ground fault protection, you will need a Dual Function (DFCI) breaker instead.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.