Eaton / Cutler-HammerJGH3175FAG
Quantity
New
Quantity
Eaton / Cutler-HammerJGH3175FAG
| Brand | Eaton / Cutler-Hammer |
|---|---|
| Part Number | JS360175A |
| Series | JS |
| Amperage | 175A |
| Poles | 3 |
| Mounting Style | Unit Mount |
| Voltage | 240VAC, 480VAC, 600VAC, 250VDC |
| Phase | 3 |
| AIC Rating | 25kA @ 240VAC, 22kA @ 480VAC, 14kA @ 600VAC, 10kA @ 250VDC |
| Terminal Type | Lugs |
|---|---|
| For Use With | Eaton / Cutler-Hammer / Westinghouse J-Frame Enclosures and Panelboards |
| Wire Gauge | 4 AWG - 350 kcmil (Al/Cu) |
| Max Wire | 350 kcmil |
| Min Wire | 4 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Adjustable Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Handle Lock |
|---|---|
| Accessories | Line and Load Lugs Included |
| Standards | UL 489, CSA C22.2 No. 5, NEMA AB-1 |
| Approval | CSA, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Reverse Feed |
This Series C breaker is compatible with Eaton, Cutler-Hammer, and legacy Westinghouse J-Frame enclosures and panelboards.
Yes, it utilizes a thermal-magnetic trip unit with a fixed thermal element for long-time overload protection and an adjustable magnetic element for instantaneous short-circuit protection.
The factory-installed line and load lugs accept 4 AWG to 350 kcmil wire and are rated for both aluminum and copper conductors.
It is a unit-mount, feed-thru breaker. It bolts directly to the enclosure backpan or mounting plate rather than plugging into a busbar.
Yes, in addition to its AC ratings, this breaker is rated for up to 250VDC applications with a 10kA interrupting capacity.
Yes. Eaton acquired the Cutler-Hammer and Westinghouse electrical distribution lines. A JS360175A breaker will fit and function identically regardless of which of these three brand names is printed on the label.
Always verify that the panel is fully de-energized before installation. Ensure that the line and load lugs are torqued to the exact specifications listed on the breaker faceplate to prevent terminal overheating.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.